ABC CABLE
ABC Cable (4 Core) to NF C 33-209 is a 0.6/1 kV aerial bundled cable made of four insulated aluminium conductors of the same section, three phases and one neutral, twisted together without a messenger. All conductors carry black cross-linked polyethylene insulation. The TDS lists 7 sizes from 4×16 to 4×120 mm².
NF C 33-209 applies to bundled insulated conductors for overhead power systems with a rated voltage of 0.6/1 kV. A bundle may include public lighting conductors and pilot conductors besides the phase and neutral conductors (NF C 33-209 Clause 1). This cable has three phases and a neutral conductor for three-phase service connections.
| Conductor | Nominal Section (mm²) | No. of Wires | Max. D.C. Resistance at 20 °C (Ω/km) | Conductor Diameter (mm) | Min. Breaking Load (kN) |
|---|---|---|---|---|---|
| Phase and neutral | 16 | 7 | 1.91 | 4.6 to 5.1 | 1.9 |
| Phase and neutral | 25 | 7 | 1.20 | 5.8 to 6.3 | 3.0 |
| Phase and neutral | 35 | 7 | 0.868 | 6.8 to 7.3 | — |
| Phase and neutral | 50 | 7 | 0.641 | 7.9 to 8.4 | — |
| Phase and neutral | 70 | 12 | 0.443 | 9.7 to 10.2 | — |
| Phase and neutral | 95 | 19 | 0.320 | 11.0 to 12.0 | — |
| Phase and neutral | 120 | 19 | 0.253 | 12.0 to 13.1 | — |
Values from Table 1 of NF C 33-209. The breaking load is a minimum value; a dash means that the standard gives no value.
The cable is not laid in the ground or under water and is not used in underground systems (Annex E of NF C 33-209).
ABC Cable (4 Core) NF C 33-209 is an aerial bundled cable built from four insulated aluminium conductors of the same section, three phases and one neutral, twisted together without a messenger. The table below gives the main design values; the dimensions, resistances and weights of each size are in the TDS tab.
| Applicable Standard | NF C 33-209 |
|---|---|
| Standard Scope | Bundled conductors with cross-linked polyethylene insulation for overhead power systems of rated voltage 0.6/1 kV |
| Rated Voltage | U0/U (Um) 0.6/1 (1.2) kV; in d.c. systems, not more than 0.9 kV to earth |
| Bundle Structure | 4 cores: 3 phases and 1 neutral of the same section; no messenger |
| Conductors | Round stranded aluminium, compacted, of purity not lower than aluminium 1350 to NF C 31-122; 16 mm² to 120 mm² |
| Wire Tensile Strength | At least 120 MPa for the aluminium wires before stranding |
| Insulation | Black extruded cross-linked polyethylene, easy to strip, weather and UV resistant |
| Breaking Load | 16 mm² at least 1.9 kN; 25 mm² at least 3.0 kN (Table 1) |
| Bundle Lay | Right-hand; maximum lay 40 cm, 45 cm, 50 cm and 55 cm for 16, 25, 35 and 50 mm² (Table 4) |
| Max. Conductor Temperature | 90 °C |
| Overall Diameter | 17.4 mm to 39.7 mm |
| Minimum Bending Radius | 18 D, D being the diameter of the largest insulated conductor; half this value for controlled bending at 15 °C or above |
Please state the cable type and size as listed in the TDS, for example 4×16 mm², the total length and the length per drum, the drum type, and any marking required in addition to the standard marking.
| No. of Cores and Section | No. of Wires | Nominal Insulation Thickness | Approx. Diameter of Cable | Max. D.C. Resistance at 20 °C | Approx. Weight |
|---|---|---|---|---|---|
| No. × mm² | No. | mm | mm | Ω/km | kg/km |
| 4×16 | 7 | 1.2 | 17.4 | 1.91 | 262 |
| 4×25 | 7 | 1.4 | 21.3 | 1.20 | 399 |
| 4×35 | 7 | 1.6 | 24.7 | 0.868 | 547 |
| 4×50 | 7 | 1.6 | 27.3 | 0.641 | 699 |
| 4×70 | 12 | 1.8 | 32.4 | 0.443 | 990 |
| 4×95 | 19 | 1.8 | 36.8 | 0.320 | 1311 |
| 4×120 | 19 | 1.8 | 39.7 | 0.253 | 1597 |