acs-Aluminum Clad Steel Conductor

BARE CONDUCTOR

ACS Conductor GB/T 1179

ACS Conductor to GB/T 1179 is a concentric lay strand made only of aluminium-clad steel wires, each a steel wire clad with aluminium. Five type codes cover five conductivity grades of GB/T 17937: JLB14, JLB20A, JLB27, JLB35 and JLB40, from 14% to 40% IACS. The TDS lists 33 code numbers from 30 to 800 for JLB14 and JLB20A, and 32 from 35 to 800 for the other three grades.

All grades share one construction for each code number, and the TDS gives linear mass, rated strength and resistance per grade. Read across the columns from JLB14 to JLB40, the linear mass, rated strength and resistance all fall as the conductivity grade rises. A type code such as JLB20A-150-19 adds the number of wires to the nominal area.

Conductor Construction

  • Aluminium-clad steel wires: Grades LB14, LB20A, LB27, LB35 and LB40 to GB/T 17937, with resistivities from 123.15 nΩ·m down to 43.10 nΩ·m (GB/T 1179 Clause 1.1)
  • Stranding: All wires are stranded concentrically in layers of opposite direction with a right-hand outer layer unless ordered otherwise; when the strand is cut, the wire ends of strands of up to 19 wires stay in place or are easily put back by hand (GB/T 1179 Clauses 5.4.1, 5.4.2 and 5.4.5)
  • Lay ratio: 10 to 16 for all layers of an aluminium-clad steel strand (GB/T 1179 Clause 5.4.4)
  • Joints: No joint of any kind is allowed in the aluminium-clad steel wires during stranding (GB/T 1179 Clause 5.5.1)
  • Rated strength: The sum of the minimum breaking loads of all wires, reduced to 95% of that sum for strands of 61 wires (GB/T 1179 Clause 5.7.1)
  • Resistance: Calculated from the resistivity of the clad wire grade given in GB/T 17937 (GB/T 1179 Clause 5.8)
  • Mass and resistance increments: The same stranding increments as an aluminium strand with the same number of wires (GB/T 1179 Clause 5.6.2)

Standard Strandings

Number of Wires Layers (excluding centre wire) JLB14 / JLB20A Code Numbers JLB27 / JLB35 / JLB40 Code Numbers Stranding Increment
7 1 30 to 95 (11) 35 to 95 (10) 1.31%
19 2 80 to 240 (8) 100 to 240 (7) 1.80%
37 3 300 to 670 (11) 300 to 670 (12) 2.04%
61 4 600 to 800 (3) 600 to 800 (3) 2.19%

Numbers in brackets are the sizes listed for each stranding. The two TDS tables follow Tables A.4 and A.5 of the standard, whose d.c. resistances are calculated values. They give calculated area, number and diameter of wires, overall diameter, and the linear mass, rated strength and resistance of each grade.

Typical Applications

  • Production of optical ground wire (OPGW)
  • Conventional stranded earth wires for overhead lines
  • Reinforcing cores for the phase conductors of overhead lines
  • Helical fittings for overhead lines
  • Uses where resistance to corrosion is an important factor

ACS Conductor to GB/T 1179 is stranded from aluminium-clad steel wires of one conductivity grade. The table below summarises the construction and calculation values of the standard; the properties of every code number are listed in the TDS tab.

Technical Characteristics

Applicable Standard GB/T 1179
Standard Scope Electrical and mechanical properties of round wire concentric lay overhead electrical stranded conductors
Type Codes JLB14, JLB20A, JLB27, JLB35, JLB40
Wires Aluminium-clad steel to GB/T 17937
Conductivity Grades 14%, 20.3%, 27%, 35% and 40% IACS
Code Numbers JLB14/JLB20A: 30 to 800, 33 sizes; JLB27/JLB35/JLB40: 35 to 800, 32 sizes
Number of Wires 7, 19, 37 or 61
Calculated Area 29.1 mm² to 805 mm²
Overall Diameter 6.9 mm to 36.9 mm
Resistivity at 20 °C LB14 123.15; LB20A 84.80; LB27 63.86; LB35 49.26; LB40 43.10 nΩ·m
Lay Ratio 10 to 16, all layers
Diameter Tolerance ±1% for diameters of 10 mm and above; ±0.1 mm below 10 mm
Linear Mass Tolerance ±2% of the listed value, grease excluded
Rated Strength Sum of the minimum wire breaking loads; 95% of the sum for 61 wires

Ordering Information

Please state the quantity; the type code, nominal area and number of wires, for example JLB20A-150-19; the length per drum and its tolerance; the packing and any special drum requirements; whether inspection is required and where; whether breaking strength, stress-strain, creep or d.c. resistance tests, or tests on wires after stranding, are required; and the direction of lay if other than right-hand.

JLB14 and JLB20A

Code Number Calculated Area No. of Wires Diameter Linear Mass Rated Strength D.C. Resistance at 20 °C
Wire Cond. JLB14 JLB20A JLB14 JLB20A JLB14 JLB20A
mm² mm mm kg/km kg/km kN kN Ω/km Ω/km
30 29.1 7 2.30 6.90 210.4 194.2 46.24 38.97 4.2899 2.9540
35 34.4 7 2.50 7.50 248.6 229.4 54.63 46.04 3.6309 2.5002
40 41.6 7 2.75 8.25 300.7 277.6 66.11 55.71 3.0008 2.0663
45 46.2 7 2.90 8.70 334.5 308.7 73.52 61.96 2.6984 1.8581
50 49.5 7 3.00 9.00 357.9 330.3 78.67 66.30 2.5215 1.7363
55 56.3 7 3.20 9.60 407.2 375.9 87.26 75.44 2.2161 1.5260
65 67.3 7 3.50 10.5 487.2 449.6 104.4 85.53 1.8525 1.2756
70 71.3 7 3.60 10.8 515.4 475.7 108.3 90.49 1.7510 1.2057
80 79.4 7 3.80 11.4 574.3 530.0 120.7 99.24 1.5716 1.0822
90 90.2 7 4.05 12.2 652.3 602.1 137.1 109.1 1.3835 0.9527
95 95.1 7 4.16 12.5 688.2 635.2 144.6 112.3 1.3113 0.9030
80 80.3 19 2.32 11.6 583.8 538.8 127.7 107.6 1.5609 1.0748
100 101 19 2.60 13.0 733.2 676.7 160.4 135.2 1.2428 0.8558
120 121 19 2.85 14.3 881.0 813.1 192.7 162.4 1.0343 0.7122
150 148 19 3.15 15.8 1076.2 993.3 229.5 198.4 0.8467 0.5830
170 173 19 3.40 17.0 1253.9 1157.3 267.4 226.0 0.7267 0.5004
185 183 19 3.50 17.5 1328.7 1226.3 283.3 232.2 0.6858 0.4722
210 210 19 3.75 18.8 1525.3 1407.8 319.0 262.3 0.5974 0.4114
240 239 19 4.00 20.0 1735.4 1601.8 362.9 288.9 0.5251 0.3616
300 298 37 3.20 22.4 2168.0 2001.0 461.2 398.7 0.4223 0.2908
350 352 37 3.48 24.4 2564.0 2366.5 545.5 446.9 0.3571 0.2459
380 377 37 3.60 25.2 2743.9 2532.5 572.5 478.3 0.3337 0.2298
400 398 37 3.70 25.9 2898.4 2675.2 604.7 497.3 0.3159 0.2175
420 420 37 3.80 26.6 3057.2 2821.7 637.8 524.5 0.2995 0.2062
450 451 37 3.94 27.6 3286.6 3033.5 685.7 563.9 0.2786 0.1918
465 465 37 4.00 28.0 3387.5 3126.6 706.7 562.6 0.2703 0.1861
500 503 37 4.16 29.1 3663.9 3381.7 764.4 593.4 0.2499 0.1721
590 588 37 4.50 31.5 4287.3 3957.1 894.5 670.8 0.2135 0.1470
600 599 37 4.54 31.9 4363.9 4027.1 910.4 682.8 0.2098 0.1445
600 600 61 3.54 32.7 4380.6 4043.2 866.9 724.4 0.2096 0.1443
630 631 61 3.63 32.7 4606.2 4251.3 911.6 761.7 0.1993 0.1373
670 670 37 4.80 33.6 4878.0 4502.3 1004.3 716.4 0.1877 0.1292
800 805 61 4.10 36.9 5876.2 5423.5 1162.9 925.8 0.1563 0.1076

JLB27, JLB35 and JLB40

Code Number Calculated Area No. of Wires Diameter Linear Mass Rated Strength D.C. Resistance at 20 °C
Wire Cond. JLB27 JLB35 JLB40 JLB27 JLB35 JLB40 JLB27 JLB35 JLB40
mm² mm mm kg/km kg/km kg/km kN kN kN Ω/km Ω/km Ω/km
35 34.4 7 2.50 7.50 205.7 179.3 161.5 37.11 27.83 23.37 1.8828 1.4524 1.2708
40 41.6 7 2.75 8.25 248.9 216.9 195.4 44.90 33.68 28.27 1.5561 1.2003 1.0502
45 46.2 7 2.90 8.70 276.8 241.2 217.3 49.94 37.45 31.44 1.3993 1.0794 0.9444
50 49.5 7 3.00 9.00 296.3 258.2 232.6 53.44 40.08 33.65 1.3075 1.0086 0.8825
55 56.3 7 3.20 9.60 337.1 293.7 264.6 60.80 45.60 38.28 1.1492 0.8865 0.7756
65 67.3 7 3.50 10.5 403.2 351.4 316.6 72.74 54.55 45.80 0.9606 0.7410 0.6483
70 71.3 7 3.60 10.8 426.6 371.8 334.9 76.95 57.71 48.45 0.9080 0.7004 0.6128
80 79.4 7 3.80 11.4 475.3 414.2 373.2 85.74 64.30 53.98 0.8149 0.6286 0.5500
90 90.2 7 4.05 12.2 539.9 470.5 423.9 97.39 73.04 61.32 0.7174 0.5534 0.4842
95 95.1 7 4.16 12.5 569.7 496.4 447.2 102.8 77.07 64.70 0.6800 0.5245 0.4589
100 101 19 2.60 13.0 606.9 528.9 476.5 108.9 81.71 68.60 0.6444 0.4971 0.4349
120 121 19 2.85 14.3 729.2 635.5 572.5 130.9 98.18 82.42 0.5363 0.4137 0.3620
150 148 19 3.15 15.8 890.8 776.3 699.4 159.9 119.9 100.7 0.4390 0.3387 0.2963
170 173 19 3.40 17.0 1037.9 904.4 814.8 186.3 139.7 117.3 0.3769 0.2907 0.2543
185 183 19 3.50 17.5 1099.8 958.4 863.5 197.4 148.1 124.3 0.3556 0.2743 0.2400
210 210 19 3.75 18.8 1262.5 1100.2 991.2 226.6 170.0 142.7 0.3098 0.2390 0.2091
240 239 19 4.00 20.0 1436.5 1251.8 1127.8 257.9 193.4 162.4 0.2723 0.2100 0.1838
300 298 37 3.20 22.4 1794.5 1563.8 1408.9 321.4 241.0 202.3 0.2190 0.1689 0.1478
350 352 37 3.48 24.4 2122.3 1849.4 1666.2 381.0 285.1 239.3 0.1852 0.1428 0.1250
380 377 37 3.60 25.2 2271.2 1979.1 1783.1 406.7 305.1 256.1 0.1730 0.1335 0.1168
400 398 37 3.70 25.9 2399.1 2090.6 1883.6 429.7 322.2 270.5 0.1638 0.1263 0.1105
420 420 37 3.80 26.6 2530.6 2205.1 1986.8 453.2 339.9 285.3 0.1553 0.1198 0.1048
450 451 37 3.94 27.6 2720.5 2370.6 2135.9 487.2 365.4 306.8 0.1444 0.1114 0.0975
465 465 37 4.00 28.0 2803.9 2443.4 2201.4 502.2 376.6 316.2 0.1401 0.1081 0.0946
500 503 37 4.16 29.1 3032.7 2642.7 2381.0 543.1 407.3 342.0 0.1296 0.1000 0.0875
510 513 37 4.20 29.4 3091.3 2693.8 2427.0 553.6 415.2 348.6 0.1271 0.0981 0.0858
590 588 37 4.50 31.5 3548.7 3092.4 2786.2 635.5 476.7 400.2 0.1107 0.0854 0.0747
600 599 37 4.54 31.9 3612.1 3147.6 2835.9 646.9 485.2 407.3 0.1088 0.0839 0.0734
600 600 61 3.54 32.7 3626.0 3159.7 2846.8 616.0 462.0 387.8 0.1087 0.0838 0.0734
630 631 61 3.63 32.7 3812.7 3322.4 2993.4 647.7 485.8 407.8 0.1034 0.0797 0.0698
670 670 37 4.80 33.6 4037.7 3518.5 3170.0 723.1 542.3 455.3 0.0973 0.0751 0.0657
800 805 61 4.10 36.9 4863.9 4238.4 3818.7 826.3 619.7 520.3 0.0810 0.0625 0.0547

Wire and Conductor Sample Tests

  • In accordance with GB/T 1179 Clauses 6.2.2 and 6.4.1, all wires are sampled before stranding and tested against their own wire standards: GB/T 17937 for the aluminium-clad steel wires.
  • In accordance with GB/T 1179 Clause 6.3, samples for the sample tests are cut at random from the outer ends of 10% of the drums, and the surface of every drum is examined before packing.
  • In accordance with GB/T 1179 Clauses 6.6.1.2 and 6.6.1.3, the conductor area is the sum of the wire areas, each worked out from the mean of three micrometer readings of the wire diameter, coating or cladding included, rounded to two decimal places.
  • In accordance with GB/T 1179 Clause 6.6.2, the overall diameter is read to 0.01 mm between the closing die and the capstan and kept within ±1% of nominal for diameters of 10 mm or more, or ±0.1 mm below 10 mm.
  • In accordance with GB/T 1179 Clause 6.6.3, the linear mass, measured to ±0.1%, is within ±2% of the value listed in the TDS.
  • In accordance with GB/T 1179 Clause 6.6.4, wires taken from the finished conductor are straightened, pulled at 25 mm/min to 100 mm/min and reach at least 95% of their tensile strength before stranding.
  • In accordance with GB/T 1179 Clause 6.6.5, where required, the resistivity of wires taken from the strand is measured on hand-straightened samples by the method of GB/T 3048.2 and meets GB/T 17937.
  • In accordance with GB/T 1179 Clauses 6.6.6 and 6.6.7, the surface shows no visible defects, and the lay ratio and direction of lay of every layer are checked against Clause 5.4.

Type Tests

  • In accordance with GB/T 1179 Clauses 6.4.3 and 6.5.2, a sample at least 400 times the conductor diameter and not shorter than 10 m carries at least 95% of the rated strength with no wire breaking; a sample failing within 1 cm of a fitting may be retested, up to three tests in all.
  • In accordance with GB/T 1179 Clause 6.5.5, the d.c. resistance at 20 °C is measured by the method of GB/T 3048.4 and does not exceed the value listed in Appendix A.
  • In accordance with GB/T 1179 Clauses 6.5.1 and 6.5.4, where agreed, a stress-strain test follows Appendix D and a creep test follows GB/T 22077 at tensions such as 15%, 25% and 35% or 40% of the rated strength.

Inspection, Packing and Marking

  • In accordance with GB/T 1179 Clauses 6.7.1 and 6.8, tests and inspection take place at the works before shipment unless agreed otherwise; a failed sample allows the lot it represents to be rejected, after which each drum of the lot may be tested once more and the conforming drums supplied.
  • In accordance with GB/T 1179 Clauses 7.1 and 7.2, the conductor is delivered on drums to JB/T 8137 with at least 30 mm clearance below the flange rim, each drum marked with the producer’s name, type code, nominal area and number of wires, direction of rotation, length, gross and net mass and month of production.
  • In accordance with GB/T 1179 Clause 7.3, unavoidable short lengths are at least 50% of the agreed production length and make up no more than 5% of the quantity delivered.