MEDIUM VOLTAGE CABLE
NA2XSRY – YJLV72 is a single-core armoured medium voltage cable with a compacted aluminium conductor, XLPE insulation, a copper tape screen, aluminium wire armour (AWA) and a PVC outer sheath, built in accordance with IEC 60502-2 for 3.6/6 (7.2) kV to 18/30 (36) kV. In the German-style code, 2X denotes XLPE insulation, S the copper screen and Y the PVC sheath, while A indicates the aluminium conductor; YJLV72 is the Chinese type code. It withstands external mechanical force and a certain tensile load.
NA2XSRY – YJLV72 has one screened core per cable with an armour layer for mechanical protection. Two extruded semi-conducting layers confine the electrical field within the XLPE insulation, and a copper tape screen forms the earthed metallic layer. A PVC separation sheath keeps the copper screen apart from the aluminium wire armour. On AC systems, IEC 60502-2 requires the armour of single-core cables to be non-magnetic unless a special construction is chosen. The XLPE insulation allows 90 °C in normal operation and 250 °C during a short circuit.
| Rated Voltage U0/U (Um) | Nominal XLPE Insulation Thickness | Cross-Sections in TDS |
|---|---|---|
| 3.6/6 (7.2) kV | 2.5 mm up to 185 mm², rising to 3.2 mm at 500 mm² and 630 mm² | 1×25 mm² to 1×630 mm² |
| 6/10 (12) kV | 3.4 mm | 1×25 mm² to 1×630 mm² |
| 8.7/15 (17.5) kV | 4.5 mm | 1×25 mm² to 1×630 mm² |
| 12/20 (24) kV | 5.5 mm | 1×35 mm² to 1×630 mm² |
| 18/30 (36) kV | 8.0 mm | 1×50 mm² to 1×630 mm² |
Choose the U0 rating from both the system voltage and the way the system clears earth faults. IEC 60502-2 Table 1 groups systems into Categories A, B and C; on a 17.5 kV system, for instance, 8.7/15 kV cable serves Categories A and B, whereas Category C calls for 12/20 kV cable. Overall diameters and weights in the TDS tab are approximate values that vary with the metallic screen and armour specified; insulation, armour and sheath dimensions are nominal values.
NA2XSRY – YJLV72 is a screened single-core armoured medium voltage cable with aluminium conductor, XLPE insulation, copper tape screen, aluminium wire armour (AWA) and PVC oversheath, built to IEC 60502-2. The characteristics below follow the voltage, material, thickness and temperature requirements of that standard; per-size dimensions, weights and conductor resistances are given in the TDS tab.
| Applicable Standard | IEC 60502-2 |
|---|---|
| Standard Scope | Extruded-insulation power cables for fixed installations at rated voltages from 6 kV (Um = 7.2 kV) up to 30 kV (Um = 36 kV) |
| Rated Voltage U0/U (Um) | 3.6/6 (7.2), 6/10 (12), 8.7/15 (17.5), 12/20 (24) and 18/30 (36) kV |
| Number of Cores | 1 |
| Conductor | Aluminium, Class 2 compacted circular to IEC 60228 |
| Nominal Cross-Section Range | 25 mm² to 630 mm²; smallest size depends on rated voltage |
| Conductor Resistance at 20 °C | Not exceeding the IEC 60228 maximum; TDS values follow IEC 60228 Table 2 |
| Conductor and Insulation Screens | Extruded semi-conducting compound |
| Insulation | XLPE, nominal thickness to IEC 60502-2 Table 6 |
| Metallic Screen | Copper tape |
| Separation Sheath | Extruded PVC between copper screen and armour |
| Armour | Round aluminium wires, nominal diameter not less than IEC 60502-2 Table 9 |
| Outer Sheath | PVC (type ST2), black as standard; nominal thickness 0.035D + 1.0 mm, minimum 1.4 mm |
| Maximum Conductor Temperature, Normal Operation | 90 °C |
| Maximum Conductor Temperature, Short Circuit | 250 °C, for a duration of not more than 5 s |
| Installation | Indoors, tunnels, cable trenches, shafts and direct burial |
Please state the rated voltage U0/U (Um), the nominal conductor cross-section, the required metallic screen cross-section or short-circuit rating, the total length and length per drum, the sheath colour if other than black and whether a strippable insulation screen is required.
| No. of Cores and Nominal Cross Section | Nominal Insulation Thickness | Nominal Aluminum Wire Diameter | Nominal Sheath Thickness | Approx. Overall Diameter | Approx. Weight | Max. D.C. Resistance of Conductor at 20°C |
|---|---|---|---|---|---|---|
| mm² | mm | mm | mm | mm | kg/km | Ω/km |
| 3.6/6(7.2)kV | ||||||
| 1×25 | 2.5 | 1.6 | 1.7 | 23.1 | 675 | 1.20 |
| 1×35 | 2.5 | 1.6 | 1.7 | 24.1 | 743 | 0.868 |
| 1×50 | 2.5 | 1.6 | 1.8 | 25.4 | 830 | 0.641 |
| 1×70 | 2.5 | 1.6 | 1.8 | 27.1 | 954 | 0.443 |
| 1×95 | 2.5 | 1.6 | 1.9 | 29.1 | 1114 | 0.320 |
| 1×120 | 2.5 | 1.6 | 1.9 | 30.3 | 1226 | 0.253 |
| 1×150 | 2.5 | 1.6 | 2.0 | 32.0 | 1375 | 0.206 |
| 1×185 | 2.5 | 2.0 | 2.1 | 34.7 | 1639 | 0.164 |
| 1×240 | 2.6 | 2.0 | 2.1 | 37.2 | 1913 | 0.125 |
| 1×300 | 2.8 | 2.0 | 2.2 | 40.0 | 2226 | 0.100 |
| 1×400 | 3.0 | 2.0 | 2.4 | 43.5 | 2655 | 0.0778 |
| 1×500 | 3.2 | 2.5 | 2.5 | 48.7 | 3329 | 0.0605 |
| 1×630 | 3.2 | 2.5 | 2.6 | 52.8 | 3960 | 0.0469 |
| 6/10(12)kV | ||||||
| 1×25 | 3.4 | 1.6 | 1.8 | 25.3 | 789 | 1.20 |
| 1×35 | 3.4 | 1.6 | 1.8 | 26.3 | 860 | 0.868 |
| 1×50 | 3.4 | 1.6 | 1.8 | 27.4 | 940 | 0.641 |
| 1×70 | 3.4 | 1.6 | 1.9 | 29.3 | 1082 | 0.443 |
| 1×95 | 3.4 | 1.6 | 1.9 | 31.1 | 1235 | 0.320 |
| 1×120 | 3.4 | 2.0 | 2.0 | 33.3 | 1440 | 0.253 |
| 1×150 | 3.4 | 2.0 | 2.1 | 35.0 | 1605 | 0.206 |
| 1×185 | 3.4 | 2.0 | 2.1 | 36.7 | 1779 | 0.164 |
| 1×240 | 3.4 | 2.0 | 2.2 | 39.2 | 2066 | 0.125 |
| 1×300 | 3.4 | 2.0 | 2.3 | 41.6 | 2353 | 0.100 |
| 1×400 | 3.4 | 2.5 | 2.4 | 45.7 | 2895 | 0.0778 |
| 1×500 | 3.4 | 2.5 | 2.5 | 49.3 | 3390 | 0.0605 |
| 1×630 | 3.4 | 2.5 | 2.6 | 53.4 | 4025 | 0.0469 |
| 8.7/15(17.5)kV | ||||||
| 1×25 | 4.5 | 1.6 | 1.8 | 27.7 | 922 | 1.20 |
| 1×35 | 4.5 | 1.6 | 1.9 | 28.9 | 1004 | 0.868 |
| 1×50 | 4.5 | 1.6 | 1.9 | 30.0 | 1094 | 0.641 |
| 1×70 | 4.5 | 1.6 | 2.0 | 31.9 | 1244 | 0.443 |
| 1×95 | 4.5 | 2.0 | 2.1 | 34.7 | 1496 | 0.320 |
| 1×120 | 4.5 | 2.0 | 2.1 | 35.9 | 1623 | 0.253 |
| 1×150 | 4.5 | 2.0 | 2.1 | 37.4 | 1769 | 0.206 |
| 1×185 | 4.5 | 2.0 | 2.2 | 39.3 | 1976 | 0.164 |
| 1×240 | 4.5 | 2.0 | 2.3 | 41.8 | 2265 | 0.125 |
| 1×300 | 4.5 | 2.0 | 2.3 | 44.0 | 2551 | 0.100 |
| 1×400 | 4.5 | 2.5 | 2.5 | 48.3 | 3132 | 0.0778 |
| 1×500 | 4.5 | 2.5 | 2.6 | 52.1 | 3665 | 0.0605 |
| 1×630 | 4.5 | 2.5 | 2.7 | 56.0 | 4295 | 0.0469 |
| 12/20(24)kV | ||||||
| 1×35 | 5.5 | 1.6 | 1.9 | 31.1 | 1140 | 0.868 |
| 1×50 | 5.5 | 1.6 | 2.0 | 32.4 | 1243 | 0.641 |
| 1×70 | 5.5 | 2.0 | 2.1 | 35.1 | 1485 | 0.443 |
| 1×95 | 5.5 | 2.0 | 2.1 | 36.9 | 1656 | 0.320 |
| 1×120 | 5.5 | 2.0 | 2.2 | 38.3 | 1796 | 0.253 |
| 1×150 | 5.5 | 2.0 | 2.2 | 39.8 | 1956 | 0.206 |
| 1×185 | 5.5 | 2.0 | 2.3 | 41.7 | 2161 | 0.164 |
| 1×240 | 5.5 | 2.0 | 2.3 | 44.0 | 2449 | 0.125 |
| 1×300 | 5.5 | 2.5 | 2.5 | 47.8 | 2937 | 0.100 |
| 1×400 | 5.5 | 2.5 | 2.6 | 50.7 | 3350 | 0.0778 |
| 1×500 | 5.5 | 2.5 | 2.7 | 54.5 | 3912 | 0.0605 |
| 1×630 | 5.5 | 2.5 | 2.8 | 58.6 | 4570 | 0.0469 |
| 18/30(36)kV | ||||||
| 1×50 | 8.0 | 2.0 | 2.2 | 38.6 | 1702 | 0.641 |
| 1×70 | 8.0 | 2.0 | 2.2 | 40.3 | 1858 | 0.443 |
| 1×95 | 8.0 | 2.0 | 2.3 | 42.3 | 2062 | 0.320 |
| 1×120 | 8.0 | 2.0 | 2.3 | 43.5 | 2204 | 0.253 |
| 1×150 | 8.0 | 2.5 | 2.4 | 46.4 | 2552 | 0.206 |
| 1×185 | 8.0 | 2.5 | 2.5 | 48.3 | 2785 | 0.164 |
| 1×240 | 8.0 | 2.5 | 2.6 | 50.8 | 3107 | 0.125 |
| 1×300 | 8.0 | 2.5 | 2.6 | 53.2 | 3450 | 0.100 |
| 1×400 | 8.0 | 2.5 | 2.8 | 56.3 | 3926 | 0.0778 |
| 1×500 | 8.0 | 2.5 | 2.8 | 59.9 | 4484 | 0.0605 |
| 1×630 | 8.0 | 2.5 | 3.0 | 64.2 | 5219 | 0.0469 |
Product Inquiry
Please send your required cable designation, number of conductors, nominal cross-section, support cable type, rated voltage, packing length, and project standard.