NA2XY – YJLV Single Core is a 0.6/1 kV power cable with an aluminium conductor, cross-linked polyethylene (XLPE) insulation and a PVC outer sheath, built in accordance with IEC 60502-1. NA2XY is the German-style type code and YJLV the Chinese type code for the same construction: the letter A marks the aluminium conductor, 2X the XLPE insulation and Y the PVC sheath. With one core per cable and a light conductor, it suits large feeders and parallel low-voltage circuits in fixed installations.
Each NA2XY – YJLV Single Core cable consists of one insulated aluminium conductor under an extruded PVC sheath, with no metallic screen or armour. The XLPE insulation permits a conductor temperature of 90 °C in continuous service. Compared with a copper cable of the same cross-section, the aluminium conductor makes the cable much lighter, which helps on long feeder runs and large sizes, at the cost of a higher conductor resistance.
| Parameter | Value |
|---|---|
| Rated voltage U0/U (Um) | 0.6/1 (1.2) kV |
| Nominal cross-sections | 1 × 2.5 mm² to 1 × 630 mm² |
| Nominal insulation thickness | 0.7 mm to 2.4 mm |
| Nominal sheath thickness | 1.4 mm to 2.2 mm |
| Approximate overall diameter | 6 mm to 39.2 mm |
| Approximate aluminium cable weight | 41 kg/km to 2292 kg/km |
Insulation and sheath thicknesses are nominal values, against which measured thicknesses are assessed during testing. Overall diameters and weights are approximate values for cable routing, drum selection and freight planning, not inspection limits. The complete list for every cross-section, with the maximum conductor resistance at 20 °C, is given in the TDS tab.
NA2XY – YJLV Single Core is a 0.6/1 kV aluminium cable with XLPE insulation and a PVC oversheath, built to IEC 60502-1. The characteristics below are taken from the voltage, material, thickness and temperature requirements of that standard; dimensions, weights and conductor resistances for each size are listed in the TDS tab.
| Applicable Standard | IEC 60502-1 |
|---|---|
| Standard Scope | Extruded-insulation power cables for fixed installations at rated voltages of 1 kV (Um = 1.2 kV) and 3 kV (Um = 3.6 kV) |
| Rated Voltage U0/U (Um) | 0.6/1 (1.2) kV |
| Number of Cores | 1 |
| Conductor | Plain aluminium, stranded circular or compacted circular |
| Nominal Cross-Section Range | 2.5 mm² to 630 mm² |
| Conductor Resistance at 20 °C | Not exceeding the maximum listed for each size in the TDS |
| Insulation | XLPE (cross-linked polyethylene) |
| Insulation Thickness | Nominal values of IEC 60502-1 Table 6, 0.6/1 kV column |
| Outer Sheath | PVC (type ST2), black as standard |
| Sheath Thickness | Nominal 0.035D + 1.0 mm, minimum 1.4 mm for single-core cables |
| Maximum Conductor Temperature, Normal Operation | 90 °C |
| Maximum Conductor Temperature, Short Circuit | 250 °C, for a duration of not more than 5 s |
| Routine Test Voltage | 3.5 kV a.c. for 5 min |
| Installation | Fixed: cable trays, conduits, wall fixing; buried with additional mechanical protection |
Please state the nominal cross-section, the total length and the length per drum, the sheath colour if other than black, any sheath marking text required, and whether purchaser inspection or witnessed tests are needed.
| No. of Cores and Nominal Cross Section | Nominal Insulation Thickness | Nominal Sheath Thickness | Approx. Overall Diameter | Approx. Weight | Max. D.C. Resistance of Conductor at 20°C |
|---|---|---|---|---|---|
| No. × mm² | mm | mm | mm | kg/km | Ω/km |
| 1×2.5 | 0.7 | 1.4 | 6.0 | 41 | 12.1 |
| 1×4 | 0.7 | 1.4 | 6.4 | 49 | 7.41 |
| 1×6 | 0.7 | 1.4 | 6.9 | 59 | 4.61 |
| 1×10 | 0.7 | 1.4 | 8.2 | 77 | 3.08 |
| 1×16 | 0.7 | 1.4 | 9.0 | 101 | 1.91 |
| 1×25 | 0.9 | 1.4 | 10.6 | 143 | 1.20 |
| 1×35 | 0.9 | 1.4 | 11.6 | 177 | 0.868 |
| 1×50 | 1.0 | 1.4 | 13.1 | 224 | 0.641 |
| 1×70 | 1.1 | 1.4 | 14.8 | 300 | 0.443 |
| 1×95 | 1.1 | 1.5 | 16.8 | 394 | 0.320 |
| 1×120 | 1.2 | 1.5 | 18.4 | 476 | 0.253 |
| 1×150 | 1.4 | 1.6 | 20.5 | 587 | 0.206 |
| 1×185 | 1.6 | 1.6 | 22.5 | 717 | 0.164 |
| 1×240 | 1.7 | 1.7 | 25.2 | 918 | 0.125 |
| 1×300 | 1.8 | 1.8 | 27.8 | 1130 | 0.100 |
| 1×400 | 2.0 | 1.9 | 31.2 | 1431 | 0.0778 |
| 1×500 | 2.2 | 2.0 | 34.7 | 1794 | 0.0605 |
| 1×630 | 2.4 | 2.2 | 39.2 | 2292 | 0.0469 |