LOW VOLTAGE CABLE
Single-core NA2XRY Cable, also designated YJLV72 under the Chinese GB standard, is a round wire armoured, aluminium-conductor, XLPE insulated, PVC sheathed low-voltage power cable manufactured in accordance with IEC 60502-1 for power networks up to and including 0.6/1 kV. Under the German VDE 0276-603 designation, NA2XRY refers to a standard-type cable (N) with aluminium conductor (A), XLPE insulation (2X), round wire armour (R) and PVC outer sheath (Y), designed for fixed installation in single-core distribution circuits requiring high tensile strength, heavy mechanical protection and reduced cable weight.
Single-core NA2XRY (YJLV72) Cable is designed as a round wire armoured low-voltage power cable for fixed installation where high tensile strength, vertical-run support and heavy mechanical protection are required, and where reduced cable weight is preferred. It consists of an aluminium conductor, XLPE insulation, an inner PVC bedding, a concentric layer of non-magnetic steel armour wires and a PVC outer sheath. The cable is suitable for cable shafts, vertical risers, mine entries, river crossings, direct burial under traction load, and any installation where the armour must also bear longitudinal mechanical stress.
| Designation | Description |
|---|---|
| NA2XRY RE | Single-core aluminium conductor, round solid (class 1), XLPE insulated, non-magnetic steel wire armoured, PVC sheathed |
| NA2XRY RM | Single-core aluminium conductor, round stranded (class 2), XLPE insulated, non-magnetic steel wire armoured, PVC sheathed |
| NA2XRY SM | Single-core aluminium conductor, shaped stranded, XLPE insulated, non-magnetic steel wire armoured, PVC sheathed (large cross-sections) |
| N2XRY | Single-core copper conductor version, XLPE insulated, non-magnetic steel wire armoured, PVC sheathed |
| NA2XBY | Single-core steel-tape armoured alternative, aluminium conductor, XLPE insulated, PVC sheathed |
| YJLV72 | Equivalent designation under Chinese GB standard: aluminium conductor, XLPE insulated, non-magnetic steel wire armoured, PVC sheathed |
For standard single-core NA2XRY (YJLV72) cable, the key distinction is the use of a concentric layer of non-magnetic steel armour wires combined with an aluminium phase conductor, providing significantly higher tensile strength than tape armour at substantially lower cable weight, rated at 0.6/1 kV (Um = 1.2 kV) in accordance with IEC 60502-1. The designation NA2XRY itself is defined under VDE 0276-603 in the German cable nomenclature system, and the equivalent designation under Chinese GB is YJLV72, where “L” identifies the aluminium conductor and “72” identifies non-magnetic round wire armour. Compared with copper-conductor N2XRY, NA2XRY offers significantly lower overall cable weight and reduced material cost, which is particularly valuable for armoured cables in long vertical runs and utility-scale installations.
The use of non-magnetic steel wire armour complies with IEC 60502-1 Clause 12.2, which requires the armour of single-core AC cables to be non-magnetic in order to avoid eddy-current and hysteresis losses. Single-core NA2XRY (YJLV72) is therefore suitable for both alternating-current and direct-current distribution circuits, while providing the highest mechanical strength among standard armoured constructions covered by IEC 60502-1.
Internationally, single-core NA2XRY is a 0.6/1 kV single-core aluminium round-wire armoured XLPE/PVC power cable defined under IEC 60502-1, and is most commonly cross-referenced with the Chinese GB designation YJLV72 (AL/XLPE/SWA/PVC) where SWA denotes single-wire armour.
Single-core NA2XRY (YJLV72) Cable is manufactured for low-voltage power distribution systems with rated voltage up to and including 0.6/1 kV, in accordance with IEC 60502-1, with cable designation NA2XRY defined under VDE 0276-603 and YJLV72 under the Chinese GB standard. The cable is intended for power distribution circuits requiring high tensile strength, heavy mechanical protection and reduced cable weight, such as vertical risers, shafts, direct burial under traction load, and crossings of rivers, roads or railways.
| Applicable Standard | IEC 60502-1; cable designation NA2XRY per VDE 0276-603, equivalent to YJLV72 under Chinese GB standard |
|---|---|
| Standard Scope | Single-core aluminium-conductor XLPE insulated, round wire armoured, PVC sheathed power cables, rated voltage up to and including 0.6/1 kV |
| Rated Voltage | U0/U = 0.6/1 kV (Um = 1.2 kV) |
| Conductor Material | Plain aluminium or aluminium alloy, class 1 (solid) or class 2 (stranded) per IEC 60228 |
| Number of Cores | 1 (single-core) |
| Insulation Material | XLPE, cross-linked polyethylene |
| Inner Covering | Extruded PVC bedding between insulation and armour |
| Armour Type | Concentric layer of non-magnetic steel wires (austenitic stainless steel or equivalent non-magnetic alloy), nominal diameter selected per IEC 60502-1 Table 9, compliant with Clause 12.2 for single-core AC applications |
| Outer Sheath Material | PVC, polyvinyl chloride, black as standard |
| Normal Operating Temperature | Maximum conductor temperature: 90°C |
| Overload Temperature | Maximum conductor temperature: 130°C |
| Short-Circuit Temperature | Maximum conductor temperature: 250°C, duration not exceeding 5 seconds |
| Installation Method | Fixed installation in cable shafts, vertical risers, mine entries, tunnels, ducts, river/road/railway crossings, or directly buried in ground including routes with longitudinal traction load |
| No. of Cores and Nominal Cross Section |
Nominal Insulation Thickness |
Nominal Non-magnetic Steel Wire Diameter |
Nominal Sheath Thickness |
Approx. Overall Diameter |
Approx. Weight | Max. D.C. Resistance of Conductor at 20℃ |
||
|---|---|---|---|---|---|---|---|---|
| Cu | Al | Cu | Al | |||||
| No. × mm² | mm | mm | mm | mm | kg/km | kg/km | Ω/km | Ω/km |
| 1×10 | 0.7 | 0.8 | 1.4 | 12.1 | 322 | 253 | 1.83 | 3.08 |
| 1×16 | 0.7 | 0.8 | 1.4 | 12.9 | 397 | 299 | 1.15 | 1.91 |
| 1×25 | 0.9 | 0.8 | 1.4 | 14.5 | 526 | 374 | 0.727 | 1.20 |
| 1×35 | 0.9 | 0.8 | 1.4 | 15.5 | 642 | 430 | 0.524 | 0.868 |
| 1×50 | 1.0 | 1.25 | 1.5 | 18.1 | 920 | 630 | 0.387 | 0.641 |
| 1×70 | 1.1 | 1.25 | 1.5 | 19.8 | 1181 | 767 | 0.268 | 0.443 |
| 1×95 | 1.1 | 1.25 | 1.6 | 21.8 | 1488 | 914 | 0.193 | 0.320 |
| 1×120 | 1.2 | 1.6 | 1.7 | 24.3 | 1922 | 1176 | 0.153 | 0.253 |
| 1×150 | 1.4 | 1.6 | 1.7 | 26.2 | 2253 | 1356 | 0.124 | 0.206 |
| 1×185 | 1.6 | 1.6 | 1.8 | 28.4 | 2705 | 1575 | 0.0991 | 0.164 |
| 1×240 | 1.7 | 1.6 | 1.9 | 31.1 | 3343 | 1876 | 0.0754 | 0.125 |
| 1×300 | 1.8 | 1.6 | 2.0 | 33.7 | 4011 | 2170 | 0.0601 | 0.100 |
| 1×400 | 2.0 | 2.0 | 2.1 | 38.3 | 5273 | 2875 | 0.0470 | 0.0778 |
| 1×500 | 2.2 | 2.0 | 2.2 | 41.8 | 6426 | 3419 | 0.0366 | 0.0605 |
| 1×630 | 2.4 | 2.0 | 2.3 | 46.1 | 7990 | 4085 | 0.0283 | 0.0469 |