NA2XRY YJLV72 cable aluminum conductor single core

LOW VOLTAGE CABLE

NA2XRY – YJLV72 (AL/XLPE/SWA/PVC) Single Core

Single-core NA2XRY Cable, also designated YJLV72 under the Chinese GB standard, is a round wire armoured, aluminium-conductor, XLPE insulated, PVC sheathed low-voltage power cable manufactured in accordance with IEC 60502-1 for power networks up to and including 0.6/1 kV. Under the German VDE 0276-603 designation, NA2XRY refers to a standard-type cable (N) with aluminium conductor (A), XLPE insulation (2X), round wire armour (R) and PVC outer sheath (Y), designed for fixed installation in single-core distribution circuits requiring high tensile strength, heavy mechanical protection and reduced cable weight.

Single-core NA2XRY (YJLV72) Cable is designed as a round wire armoured low-voltage power cable for fixed installation where high tensile strength, vertical-run support and heavy mechanical protection are required, and where reduced cable weight is preferred. It consists of an aluminium conductor, XLPE insulation, an inner PVC bedding, a concentric layer of non-magnetic steel armour wires and a PVC outer sheath. The cable is suitable for cable shafts, vertical risers, mine entries, river crossings, direct burial under traction load, and any installation where the armour must also bear longitudinal mechanical stress.

Cable Construction

  • Conductor: Plain aluminium or aluminium alloy, class 1 (solid) or class 2 (stranded), constructed according to IEC 60228.
  • Insulation: Extruded cross-linked polyethylene (XLPE), suitable for a maximum conductor temperature of 90 °C in normal operation.
  • Inner covering (bedding): Extruded PVC applied over the insulation, providing a separation layer and a bed for the armour.
  • Armour: A concentric layer of non-magnetic steel wires (austenitic stainless steel or equivalent non-magnetic alloy), closely applied with a minimum gap between adjacent wires, in nominal diameters of 0.8 / 1.25 / 1.6 / 2.0 / 2.5 / 3.15 mm selected per IEC 60502-1 Table 9.
  • Outer sheath: Extruded PVC applied over the armour, providing mechanical, moisture and chemical protection.

NA2XRY Cable Designations

Designation Description
NA2XRY RE Single-core aluminium conductor, round solid (class 1), XLPE insulated, non-magnetic steel wire armoured, PVC sheathed
NA2XRY RM Single-core aluminium conductor, round stranded (class 2), XLPE insulated, non-magnetic steel wire armoured, PVC sheathed
NA2XRY SM Single-core aluminium conductor, shaped stranded, XLPE insulated, non-magnetic steel wire armoured, PVC sheathed (large cross-sections)
N2XRY Single-core copper conductor version, XLPE insulated, non-magnetic steel wire armoured, PVC sheathed
NA2XBY Single-core steel-tape armoured alternative, aluminium conductor, XLPE insulated, PVC sheathed
YJLV72 Equivalent designation under Chinese GB standard: aluminium conductor, XLPE insulated, non-magnetic steel wire armoured, PVC sheathed

For standard single-core NA2XRY (YJLV72) cable, the key distinction is the use of a concentric layer of non-magnetic steel armour wires combined with an aluminium phase conductor, providing significantly higher tensile strength than tape armour at substantially lower cable weight, rated at 0.6/1 kV (Um = 1.2 kV) in accordance with IEC 60502-1. The designation NA2XRY itself is defined under VDE 0276-603 in the German cable nomenclature system, and the equivalent designation under Chinese GB is YJLV72, where “L” identifies the aluminium conductor and “72” identifies non-magnetic round wire armour. Compared with copper-conductor N2XRY, NA2XRY offers significantly lower overall cable weight and reduced material cost, which is particularly valuable for armoured cables in long vertical runs and utility-scale installations.

The use of non-magnetic steel wire armour complies with IEC 60502-1 Clause 12.2, which requires the armour of single-core AC cables to be non-magnetic in order to avoid eddy-current and hysteresis losses. Single-core NA2XRY (YJLV72) is therefore suitable for both alternating-current and direct-current distribution circuits, while providing the highest mechanical strength among standard armoured constructions covered by IEC 60502-1.

Typical Applications

  • Vertical cable runs and shafts where the armour must bear the cable’s own weight
  • Cable risers in high-rise buildings, mine entries and offshore structures
  • Direct burial in soils subject to settlement, traction or longitudinal stress
  • River, road and railway crossings requiring high tensile load capacity
  • Low-voltage AC distribution circuits up to 0.6/1 kV with heavy mechanical protection
  • Utility-scale distribution feeders where weight and cost are critical factors

Internationally, single-core NA2XRY is a 0.6/1 kV single-core aluminium round-wire armoured XLPE/PVC power cable defined under IEC 60502-1, and is most commonly cross-referenced with the Chinese GB designation YJLV72 (AL/XLPE/SWA/PVC) where SWA denotes single-wire armour.

Single-core NA2XRY (YJLV72) Cable is manufactured for low-voltage power distribution systems with rated voltage up to and including 0.6/1 kV, in accordance with IEC 60502-1, with cable designation NA2XRY defined under VDE 0276-603 and YJLV72 under the Chinese GB standard. The cable is intended for power distribution circuits requiring high tensile strength, heavy mechanical protection and reduced cable weight, such as vertical risers, shafts, direct burial under traction load, and crossings of rivers, roads or railways.

Technical Characteristics

Applicable Standard IEC 60502-1; cable designation NA2XRY per VDE 0276-603, equivalent to YJLV72 under Chinese GB standard
Standard Scope Single-core aluminium-conductor XLPE insulated, round wire armoured, PVC sheathed power cables, rated voltage up to and including 0.6/1 kV
Rated Voltage U0/U = 0.6/1 kV (Um = 1.2 kV)
Conductor Material Plain aluminium or aluminium alloy, class 1 (solid) or class 2 (stranded) per IEC 60228
Number of Cores 1 (single-core)
Insulation Material XLPE, cross-linked polyethylene
Inner Covering Extruded PVC bedding between insulation and armour
Armour Type Concentric layer of non-magnetic steel wires (austenitic stainless steel or equivalent non-magnetic alloy), nominal diameter selected per IEC 60502-1 Table 9, compliant with Clause 12.2 for single-core AC applications
Outer Sheath Material PVC, polyvinyl chloride, black as standard
Normal Operating Temperature Maximum conductor temperature: 90°C
Overload Temperature Maximum conductor temperature: 130°C
Short-Circuit Temperature Maximum conductor temperature: 250°C, duration not exceeding 5 seconds
Installation Method Fixed installation in cable shafts, vertical risers, mine entries, tunnels, ducts, river/road/railway crossings, or directly buried in ground including routes with longitudinal traction load
No. of Cores and
Nominal Cross Section
Nominal
Insulation
Thickness
Nominal Non-magnetic
Steel Wire Diameter
Nominal
Sheath
Thickness
Approx.
Overall Diameter
Approx. Weight Max. D.C. Resistance
of Conductor at 20℃
Cu Al Cu Al
No. × mm² mm mm mm mm kg/km kg/km Ω/km Ω/km
1×10 0.7 0.8 1.4 12.1 322 253 1.83 3.08
1×16 0.7 0.8 1.4 12.9 397 299 1.15 1.91
1×25 0.9 0.8 1.4 14.5 526 374 0.727 1.20
1×35 0.9 0.8 1.4 15.5 642 430 0.524 0.868
1×50 1.0 1.25 1.5 18.1 920 630 0.387 0.641
1×70 1.1 1.25 1.5 19.8 1181 767 0.268 0.443
1×95 1.1 1.25 1.6 21.8 1488 914 0.193 0.320
1×120 1.2 1.6 1.7 24.3 1922 1176 0.153 0.253
1×150 1.4 1.6 1.7 26.2 2253 1356 0.124 0.206
1×185 1.6 1.6 1.8 28.4 2705 1575 0.0991 0.164
1×240 1.7 1.6 1.9 31.1 3343 1876 0.0754 0.125
1×300 1.8 1.6 2.0 33.7 4011 2170 0.0601 0.100
1×400 2.0 2.0 2.1 38.3 5273 2875 0.0470 0.0778
1×500 2.2 2.0 2.2 41.8 6426 3419 0.0366 0.0605
1×630 2.4 2.0 2.3 46.1 7990 4085 0.0283 0.0469
Download Datasheet PDF

Electrical Tests

  • Conductor resistance test
  • AC voltage test (3.5 kV, 5 min) on every manufactured length
  • Insulation resistance test at ambient temperature
  • Insulation resistance test at maximum operating temperature (90 °C)
  • Spark test on the PVC inner covering (bedding)
  • 4-hour voltage test (type test)

Mechanical Tests

  • Tensile strength and elongation tests on XLPE insulation and PVC sheath before and after ageing
  • Low-temperature bending and impact tests on insulation and sheath
  • Measurement of round armour wire diameter against IEC 60502-1 Table 9
  • Verification of armour closure (minimum gap between adjacent wires)
  • Tensile test on armour wires

Physical and Material Tests

  • Hot set test for XLPE insulation
  • Pressure test at high temperature for PVC inner covering and outer sheath
  • Heat shock (crack resistance) test for PVC inner covering and outer sheath
  • Shrinkage test for XLPE insulation and PVC sheath
  • Corrosion-resistance check of armour wires

Product Inquiry

Request a Quote

Please send your required cable designation, number of conductors, nominal cross-section, support cable type, rated voltage, packing length, and project standard.

Selected Product: NA2XRY – YJLV72 (AL/XLPE/SWA/PVC) Single Core