N2XBY YJV22 cable copper conductor 3 core

LOW VOLTAGE CABLE

N2XBY – YJV22 (CU/XLPE/STA/PVC) Multi Core

Multi core N2XBY Cable is a steel-tape armoured, copper-conductor, XLPE insulated, PVC sheathed low-voltage power cable manufactured in accordance with IEC 60502-1 for power networks up to and including 0.6/1 kV. Under the German VDE 0276-603 designation, N2XBY refers to a standard-type cable (N) with XLPE insulation (2X), steel tape armour (B) and PVC outer sheath (Y), designed for three-phase power distribution circuits in installations exposed to impact, crushing, vibration or rodent damage.

Multi core N2XBY Cable is designed as a steel-tape armoured low-voltage power cable for three-phase distribution circuits in fixed installations where additional mechanical protection is required. It consists of three copper conductors, individually XLPE insulated and identified by colour, laid up together with non-hygroscopic fillers, covered by an inner PVC bedding, double steel-tape armour and a PVC outer sheath. The cable can be installed in tunnels, ducts, conduits, in masonry or directly buried in ground, including stony soils, industrial sites and routes with rodent risk.

Cable Construction

  • Conductor: Plain annealed copper, class 1 (solid) or class 2 (stranded), constructed according to IEC 60228.
  • Insulation: Extruded cross-linked polyethylene (XLPE), suitable for a maximum conductor temperature of 90 °C in normal operation.
  • Core identification: By colour according to VDE 0293-308 (typical arrangement: brown / black / grey, plus green-yellow for the protective earth conductor in N2XBY-J).
  • Laid-up cores: Three insulated cores cabled together with non-hygroscopic fillers to form a substantially circular cross-section.
  • Inner covering (bedding): Extruded PVC applied over the laid-up cores, providing a bed for the armour.
  • Armour: Two helically-applied steel tape layers, with the outer tape approximately centred over the gap of the inner tape, in accordance with IEC 60502-1 Clause 12.7.
  • Outer sheath: Extruded PVC applied over the armour, providing mechanical, moisture and chemical protection.

N2XBY Cable Designations

Designation Description
N2XBY-J 3× Multi core copper conductor, XLPE insulated, double steel-tape armoured, PVC sheathed, with green-yellow protective earth conductor
N2XBY-O 3× Multi core copper conductor, XLPE insulated, double steel-tape armoured, PVC sheathed, without protective earth conductor
N2XBY 3× RE Multi core copper conductor, round solid (class 1), XLPE insulated, double steel-tape armoured, PVC sheathed
N2XBY 3× RM Multi core copper conductor, round stranded (class 2), XLPE insulated, double steel-tape armoured, PVC sheathed
N2XBY 3× SM Multi core copper conductor, shaped stranded, XLPE insulated, double steel-tape armoured, PVC sheathed (large cross-sections)
NA2XBY 3× Multi core aluminium conductor version, XLPE insulated, double steel-tape armoured, PVC sheathed

For standard Multi core N2XBY cable, the key distinction is the combination of three copper phase conductors with XLPE thermoset insulation, double steel-tape armour and a PVC outer sheath, rated at 0.6/1 kV (Um = 1.2 kV) in accordance with IEC 60502-1. The designation N2XBY itself is defined under VDE 0276-603 in the German cable nomenclature system.

In a Multi core armoured construction, the alternating currents of the three phases sum to zero, so the magnetic fluxes through the armour are cancelled and no significant eddy-current or hysteresis losses are induced. Ordinary galvanized steel tape can therefore be used for the armour, providing full mechanical protection without the non-magnetic armour requirement that applies to single-core AC cables under IEC 60502-1 Clause 12.2.

Typical Applications

  • Three-phase low-voltage power distribution networks up to 0.6/1 kV
  • Industrial plants, factories and process facilities requiring mechanical protection
  • Substations, switchrooms and main distribution feeders
  • Direct burial in stony, uneven or aggressive soil
  • Cable tunnels, ducts, conduits and underground cable channels with rodent risk
  • Locations exposed to impact, crushing, vibration or heavy mechanical stress

Internationally, Multi core N2XBY is a 0.6/1 kV Multi core steel-tape armoured XLPE/PVC power cable defined under IEC 60502-1, and is often cross-referenced with designations such as CU/XLPE/STA/PVC 3-core and YJV22 3× under the Chinese GB standard.

Multi core N2XBY Cable is manufactured for low-voltage three-phase power distribution systems with rated voltage up to and including 0.6/1 kV, in accordance with IEC 60502-1, with cable designation N2XBY defined under VDE 0276-603. The cable is intended for power distribution circuits requiring additional mechanical protection and is suitable for fixed installation in tunnels, ducts, direct burial and industrial environments.

Technical Characteristics

Applicable Standard IEC 60502-1; cable designation N2XBY per VDE 0276-603
Standard Scope Multi core XLPE insulated, steel-tape armoured, PVC sheathed power cables, rated voltage up to and including 0.6/1 kV
Rated Voltage U0/U = 0.6/1 kV (Um = 1.2 kV)
Conductor Material Plain annealed copper, class 1 (solid) or class 2 (stranded) per IEC 60228
Number of Cores 3
Core Identification By colour per VDE 0293-308 (with or without green-yellow protective earth conductor)
Insulation Material XLPE, cross-linked polyethylene
Inner Covering Extruded PVC bedding over the laid-up cores
Armour Type Double galvanized steel tape, helically applied per IEC 60502-1 Clause 12.7
Outer Sheath Material PVC, polyvinyl chloride, black as standard
Normal Operating Temperature Maximum conductor temperature: 90°C
Overload Temperature Maximum conductor temperature: 130°C
Short-Circuit Temperature Maximum conductor temperature: 250°C, duration not exceeding 5 seconds
Installation Method Fixed installation in tunnels, ducts, conduits, cable channels, or directly buried in ground including stony and mechanically demanding routes
No. of Cores and
Nominal Cross Section
Nominal
Insulation
Thickness
Nominal Galvanized
Steel Tape Thickness
Nominal
Sheath
Thickness
Approx.
Overall Diameter
Approx. Weight Max. D.C. Resistance
of Conductor at 20℃
Cu Al Cu Al
No. × mm² mm mm mm mm kg/km kg/km Ω/km Ω/km
2×1.5 0.7 0.2 1.8 12.2 220 12.1
2×2.5 0.7 0.2 1.8 13.0 256 228 7.41 12.1
2×4 0.7 0.2 1.8 14.0 307 260 4.61 7.41
2×6 0.7 0.2 1.8 15.0 370 300 3.08 4.61
2×10 0.7 0.2 1.8 17.5 509 373 1.83 3.08
2×16 0.7 0.2 1.8 19.1 659 461 1.15 1.91
2×25 0.9 0.2 1.8 22.3 915 609 0.727 1.20
2×35 0.9 0.2 1.8 24.3 1147 722 0.524 0.868
2×50 1.0 0.2 1.8 27.3 1463 874 0.387 0.641
2×70 1.1 0.2 1.9 30.9 1939 1106 0.268 0.443
2×95 1.1 0.2 2.0 35.4 2587 1433 0.193 0.320
2×120 1.2 0.5 2.2 40.2 3557 2078 0.153 0.253
2×150 1.4 0.5 2.3 44.2 4269 2465 0.124 0.206
2×185 1.6 0.5 2.5 49.0 5250 2977 0.0991 0.164
2×240 1.7 0.5 2.6 54.2 6551 3603 0.0754 0.125
2×300 1.8 0.5 2.8 59.8 8038 4330 0.0601 0.100
2×400 2.0 0.5 3.0 66.6 10056 5268 0.0470 0.0778
3×1.5 0.7 0.2 1.8 12.7 246 12.1
3×2.5 0.7 0.2 1.8 13.5 292 249 7.41 12.1
3×4 0.7 0.2 1.8 14.5 359 287 4.61 7.41
3×6 0.7 0.2 1.8 15.6 441 335 3.08 4.61
3×10 0.7 0.2 1.8 18.4 621 422 1.83 3.08
3×16 0.7 0.2 1.8 20.1 827 529 1.15 1.91
3×25 0.9 0.2 1.8 23.5 1170 711 0.727 1.20
3×35 0.9 0.2 1.8 25.7 1491 853 0.524 0.868
3×50 1.0 0.2 1.8 28.9 1922 1045 0.387 0.641
3×70 1.1 0.2 2.0 33.7 2657 1409 0.268 0.443
3×95 1.1 0.5 2.2 39.2 3884 2153 0.193 0.320
3×120 1.2 0.5 2.3 42.9 4728 2517 0.153 0.253
3×150 1.4 0.5 2.4 47.6 5749 3043 0.124 0.206
3×185 1.6 0.5 2.6 52.3 7049 3636 0.0991 0.164
3×240 1.7 0.5 2.7 58.3 8927 4504 0.0754 0.125
3×300 1.8 0.5 2.9 63.9 10919 5362 0.0601 0.100
3×400 2.0 0.5 3.2 71.4 13772 6602 0.0470 0.0778
4×1.5 0.7 0.2 1.8 13.4 279 12.1
4×2.5 0.7 0.2 1.8 14.3 336 278 7.41 12.1
4×4 0.7 0.2 1.8 15.5 420 325 4.61 7.41
4×6 0.7 0.2 1.8 16.7 525 383 3.08 4.61
4×10 0.7 0.2 1.8 19.8 751 487 1.83 3.08
4×16 0.7 0.2 1.8 21.7 1016 619 1.15 1.91
4×25 0.9 0.2 1.8 25.6 1455 843 0.727 1.20
4×35 0.9 0.2 1.8 28.0 1871 1021 0.524 0.868
4×50 1.0 0.2 1.9 31.8 2440 1274 0.387 0.641
4×70 1.1 0.2 2.1 37.0 3387 1723 0.268 0.443
4×95 1.1 0.5 2.3 43.0 4907 2599 0.193 0.320
4×120 1.2 0.5 2.4 47.5 6044 3100 0.153 0.253
4×150 1.4 0.5 2.6 52.5 7332 3724 0.124 0.206
4×185 1.6 0.5 2.7 57.9 9048 4503 0.0991 0.164
4×240 1.7 0.5 2.9 64.4 11449 5552 0.0754 0.125
4×300 1.8 0.5 3.1 70.6 14041 6634 0.0601 0.100
4×400 2.0 0.5 3.4 79.3 17835 8279 0.0470 0.0778
5×1.5 0.7 0.2 1.8 14.2 314 12.1
5×2.5 0.7 0.2 1.8 15.2 383 311 7.41 12.1
5×4 0.7 0.2 1.8 16.5 485 365 4.61 7.41
5×6 0.7 0.2 1.8 17.9 613 434 3.08 4.61
5×10 0.7 0.2 1.8 21.3 886 558 1.83 3.08
5×16 0.7 0.2 1.8 23.4 1212 717 1.15 1.91
5×25 0.9 0.2 1.8 27.8 1751 985 0.727 1.20
5×35 0.9 0.2 1.9 30.7 2277 1214 0.524 0.868
5×50 1.0 0.2 2.0 35.6 3029 1571 0.387 0.641
5×70 1.1 0.5 2.3 42.0 4551 2470 0.268 0.443
5×95 1.1 0.5 2.4 47.5 6006 3121 0.193 0.320
5×120 1.2 0.5 2.5 52.0 7354 3677 0.153 0.253
5×150 1.4 0.5 2.7 57.9 8999 4489 0.124 0.206
5×185 1.6 0.5 2.9 63.7 11074 5393 0.0991 0.164
5×240 1.7 0.5 3.1 70.9 14042 6670 0.0754 0.125
5×300 1.8 0.5 3.4 78.3 17364 8106 0.0601 0.100
5×400 2.0 0.8 3.7 88.8 22823 10874 0.0470 0.0778
3×2.5+1×1.5 0.7/0.7 0.2 1.8 14.1 322 7.41/12.1
3×4+1×2.5 0.7/0.7 0.2 1.8 15.2 399 313 4.61/7.41 7.41/12.1
3×6+1×4 0.7/0.7 0.2 1.8 16.4 499 368 3.08/4.61 4.61/7.41
3×10+1×6 0.7/0.7 0.2 1.8 19.0 694 461 1.83/3.08 3.08/4.61
3×16+1×10 0.7/0.7 0.2 1.8 21.2 949 586 1.15/1.83 1.91/3.08
3×25+1×16 0.9/0.7 0.2 1.8 24.6 1344 786 0.727/1.15 1.20/1.91
3×35+1×16 0.9/0.7 0.2 1.8 26.4 1653 917 0.524/1.15 0.868/1.91
3×50+1×25 1.0/0.9 0.2 1.9 30.3 2194 1166 0.387/0.727 0.641/1.20
3×70+1×35 1.1/0.9 0.2 2.0 34.9 3005 1545 0.268/0.524 0.443/0.868
3×95+1×50 1.1/1.0 0.5 2.2 40.7 4369 2344 0.193/0.387 0.320/0.641
3×120+1×70 1.2/1.1 0.5 2.3 44.8 5424 2801 0.153/0.268 0.253/0.443
3×150+1×70 1.4/1.1 0.5 2.5 49.1 6433 3311 0.124/0.268 0.206/0.443
3×185+1×95 1.6/1.1 0.5 2.6 54.0 7959 3974 0.0991/0.193 0.164/0.320
3×240+1×120 1.7/1.2 0.5 2.8 60.3 10095 4934 0.0754/0.153 0.125/0.253
3×300+1×150 1.8/1.4 0.5 3.0 66.2 12359 5903 0.0601/0.124 0.100/0.206
3×400+1×185 2.0/1.6 0.5 3.2 74.0 15608 7306 0.0470/0.0991 0.0778/0.164
3×2.5+2×1.5 0.7/0.7 0.2 1.8 14.8 355 7.41/12.1
3×4+2×2.5 0.7/0.7 0.2 1.8 16.0 444 343 4.61/7.41 7.41/12.1
3×6+2×4 0.7/0.7 0.2 1.8 17.3 562 406 3.08/4.61 4.61/7.41
3×10+2×6 0.7/0.7 0.2 1.8 19.9 776 508 1.83/3.08 3.08/4.61
3×16+2×10 0.7/0.7 0.2 1.8 22.6 1081 653 1.15/1.83 1.91/3.08
3×25+2×16 0.9/0.7 0.2 1.8 26.0 1532 875 0.727/1.15 1.20/1.91
3×35+2×16 0.9/0.7 0.2 1.8 27.7 1836 1001 0.524/1.15 0.868/1.91
3×50+2×25 1.0/0.9 0.2 1.9 32.7 2525 1332 0.387/0.727 0.641/1.20
3×70+2×35 1.1/0.9 0.2 2.1 36.9 3399 1726 0.268/0.524 0.443/0.868
3×95+2×50 1.1/1.0 0.5 2.3 43.1 4917 2599 0.193/0.387 0.320/0.641
3×120+2×70 1.2/1.1 0.5 2.4 48.1 6235 3198 0.153/0.268 0.253/0.443
3×150+2×70 1.4/1.1 0.5 2.5 51.4 7165 3627 0.124/0.268 0.206/0.443
3×185+2×95 1.6/1.1 0.5 2.7 57.4 9040 4478 0.0991/0.193 0.164/0.320
3×240+2×120 1.7/1.2 0.5 2.9 63.5 11363 5467 0.0754/0.153 0.125/0.253
3×300+2×150 1.8/1.4 0.5 3.1 69.9 13917 6560 0.0601/0.124 0.100/0.206
3×400+2×185 2.0/1.6 0.5 3.4 78.2 17581 8146 0.0470/0.0991 0.0778/0.164
4×2.5+1×1.5 0.7/0.7 0.2 1.8 15.0 369 7.41/12.1
4×4+1×2.5 0.7/0.7 0.2 1.8 16.2 464 354 4.61/7.41 7.41/12.1
4×6+1×4 0.7/0.7 0.2 1.8 17.6 587 420 3.08/4.61 4.61/7.41
4×10+1×6 0.7/0.7 0.2 1.8 20.6 831 533 1.83/3.08 3.08/4.61
4×16+1×10 0.7/0.7 0.2 1.8 23.0 1147 684 1.15/1.83 1.91/3.08
4×25+1×16 0.9/0.7 0.2 1.8 26.9 1455 930 0.727/1.15 1.20/1.91
4×35+1×16 0.9/0.7 0.2 1.8 29.1 2049 1100 0.524/1.15 0.868/1.91
4×50+1×25 1.0/0.9 0.2 2.0 34.3 2783 1464 0.387/0.727 0.641/1.20
4×70+1×35 1.1/0.9 0.5 2.2 40.1 4152 2275 0.268/0.524 0.443/0.868
4×95+1×50 1.1/1.0 0.5 2.3 45.0 5427 2825 0.193/0.387 0.320/0.641
4×120+1×70 1.2/1.1 0.5 2.5 50.1 6804 3447 0.153/0.268 0.253/0.443
4×150+1×70 1.4/1.1 0.5 2.6 54.4 8047 4023 0.124/0.268 0.206/0.443
4×185+1×95 1.6/1.1 0.5 2.7 60.5 10052 4931 0.0991/0.193 0.164/0.320
4×240+1×120 1.7/1.2 0.5 3.0 67.2 12697 6062 0.0754/0.153 0.125/0.253
4×300+1×150 1.8/1.4 0.5 3.2 74.2 15654 7346 0.0601/0.124 0.100/0.206
4×400+1×185 2.0/1.6 0.8 3.6 84.2 20594 9900 0.0470/0.0991 0.0778/0.164
Download Datasheet PDF

Electrical Tests

  • Conductor resistance test on each core
  • AC voltage test (3.5 kV, 5 min) between conductors and between each conductor and armour / earth
  • Insulation resistance test at ambient temperature
  • Insulation resistance test at maximum operating temperature (90 °C)
  • Spark test on the PVC inner covering (bedding)
  • 4-hour voltage test (type test)

Mechanical Tests

  • Tensile strength and elongation tests on XLPE insulation and PVC sheath before and after ageing
  • Low-temperature bending and impact tests on insulation and sheath
  • Measurement of steel-tape armour thickness against IEC 60502-1 Table 10
  • Verification of armour overlap and gap between adjacent turns of each tape

Physical and Material Tests

  • Hot set test for XLPE insulation
  • Pressure test at high temperature for PVC inner covering and outer sheath
  • Heat shock (crack resistance) test for PVC inner covering and outer sheath
  • Shrinkage test for XLPE insulation and PVC sheath
  • Galvanizing / corrosion-resistance check of steel armour tapes