OVERHEAD INSULATED CABLE
PVC Covered Conductor to BS 6485 is a stranded overhead line conductor with an extruded PVC covering. The covering guards against accidental contact where the line crosses or runs close to telecommunication lines, or passes within reach of buildings. Two grades are made: Type 8 with a 0.8 mm black covering and Type 16 with a 1.6 mm green covering, on copper, aluminium, steel-reinforced aluminium and aluminium alloy conductors.
BS 6485 standardizes PVC-covered conductors for overhead power lines by the minimum thickness of the covering (BS 6485 Clause 1). The covering guards against contact at crossings of and proximities to telecommunication lines and, for Type 8, on lines within reach of buildings, under the operating conditions below (BS 6485 Clause 1).
| Type | Minimum Covering Thickness | Colour | Operating Voltage | Suitable For |
|---|---|---|---|---|
| Type 8 | 0.8 mm | Black | Not above 650 V r.m.s. between conductors or 250 V r.m.s. to earth | Crossings of and proximities to telecommunication lines; lines, especially service lines, within reach of buildings |
| Type 16 | 1.6 mm | Green | Above 650 V r.m.s. between conductors or 250 V r.m.s. to earth, normally not above 11 kV between conductors or 6.6 kV to earth | Crossings of and proximities to telecommunication lines |
For Type 16, a system neutral earthed through an arc-suppression coil is acceptable where earth faults are cleared without undue delay (BS 6485 Clause 1).
| Conductor | Annex B Table | Type | Nominal Cross-Sections | Stranding |
|---|---|---|---|---|
| AAC/PVC (aluminium) | B.3 | Type 8 | 22 to 200 mm² (Midge to Chafer) | 7/2.06 to 19/3.78 |
| CU/PVC (hard-drawn copper) | B.1 | Type 8 and Type 16 | 14 to 100 mm² | 3 or 7 wires |
| ACSR/PVC (aluminium, steel reinforced) | B.4 | Type 16 | 25 to 200 mm² | 6/1, 6/7, 18/1 and 30/7 aluminium/steel wires |
| AAAC/PVC (aluminium alloy) | B.5 | Type 16 | 25 to 175 mm² | 7/2.34 to 19/3.76 |
Overall diameters, masses and breaking loads in the TDS are approximate values and not requirements of the standard (BS 6485 Clause 3.2). The resistance of copper conductors is a maximum value; for aluminium, steel-reinforced aluminium and aluminium alloy conductors the tables of the standard give a calculated resistance.
PVC Covered Conductor to BS 6485 carries an extruded PVC covering over a stranded overhead line conductor. The table below summarises the requirements of the standard; the particulars of every size are listed in the TDS tab.
| Applicable Standard | BS 6485 |
|---|---|
| Standard Scope | PVC-covered conductors for overhead power lines |
| Types | Type 8 (0.8 mm covering) and Type 16 (1.6 mm covering) |
| Conductors | Copper to BS 7884; aluminium and steel-reinforced aluminium to BS 215; aluminium alloy to BS 3242 |
| Covering | PVC compound type TI 1 to BS 7655-3.1 |
| Colour | Type 8 black; Type 16 green |
| Voltage, Type 8 | Up to 650 V r.m.s. between conductors, 250 V r.m.s. to earth |
| Voltage, Type 16 | Normally up to 11 kV between conductors, 6.6 kV to earth |
| Spark Test | 6 kV a.c. or 9 kV d.c. (Type 8); 12 kV a.c. or 18 kV d.c. (Type 16) |
| High Voltage Test | 25 kV a.c. for 5 min after water immersion (Type 16) |
| Insulation Resistance | More than 0.5 MΩ for 1 km of conductor (Type 16) |
| Test Conditions | Ambient 5 °C to 35 °C; a.c. test voltages at 49 Hz to 61 Hz |
Please state the type (Type 8 or Type 16); the conductor material and nominal cross-section, or the code word for aluminium conductors; the quantity and the length per drum; and whether purchaser inspection or witnessed tests are needed.
| Code Word | Nominal Cross-Sectional Area | Stranding and Wire Diameter | Approx. Diameter of Bare Conductor | Calculated Resistance at 20 °C | Approx. Breaking Load | Approx. Overall Diameter | Approx. Mass |
|---|---|---|---|---|---|---|---|
| Type 8 | Type 8 | ||||||
| mm² | No./mm | mm | Ω/km | kN | mm | kg/km | |
| Midge | 22 | 7/2.06 | 6.18 | 1.227 | 3.99 | 8.2 | 100 |
| Ant | 50 | 7/3.10 | 9.30 | 0.5419 | 8.28 | 11.7 | 200 |
| Wasp | 100 | 7/4.39 | 13.17 | 0.2702 | 16.00 | 16.0 | 360 |
| Chafer | 200 | 19/3.78 | 18.9 | 0.1349 | 32.40 | 21.7 | 690 |
| Nominal Cross-Sectional Area | Stranding and Wire Diameter | Approx. Diameter of Bare Conductor | Max. D.C. Resistance at 20 °C | Approx. Breaking Load | Approx. Overall Diameter | Approx. Mass | ||
|---|---|---|---|---|---|---|---|---|
| Type 8 | Type 16 | Type 8 | Type 16 | |||||
| mm² | No./mm | mm | Ω/km | kN | mm | mm | kg/km | kg/km |
| 14 | 7/1.60 | 4.80 | 1.303 | 5.744 | 6.8 | 8.4 | 160 | 190 |
| 16 | 3/2.65 | 5.70 | 1.106 | 6.590 | 7.7 | 9.3 | 180 | 220 |
| 32 | 3/3.75 | 8.06 | 0.5520 | 12.71 | 10.5 | 12.1 | 350 | 390 |
| 35 | 7/2.50 | 7.50 | 0.5337 | 14.097 | 9.9 | 11.5 | 360 | 400 |
| 70 | 7/3.55 | 10.65 | 0.2646 | 26.88 | 13.5 | 14.7 | 690 | 750 |
| 100 | 7/4.30 | 12.90 | 0.1810 | 37.64 | 15.7 | 16.9 | 990 | 1060 |
| Nominal Cross-Sectional Area | Stranding and Wire Diameter | Approx. Diameter of Bare Conductor | Calculated Resistance at 20 °C | Approx. Breaking Load | Approx. Overall Diameter | Approx. Mass | |
|---|---|---|---|---|---|---|---|
| Aluminium | Steel | Type 16 | Type 16 | ||||
| mm² | No./mm | No./mm | mm | Ω/km | kN | mm | kg/km |
| 25 | 6/2.36 | 1/2.36 | 7.08 | 1.093 | 9.61 | 10.7 | 190 |
| 50 | 6/3.35 | 1/3.35 | 10.05 | 0.5426 | 18.35 | 14.1 | 330 |
| 100 | 6/4.72 | 7/1.57 | 14.15 | 0.2733 | 32.70 | 18.2 | 550 |
| 150 | 30/2.59 | 7/2.59 | 18.13 | 0.1828 | 69.20 | 22.2 | 920 |
| 150 | 18/3.35 | 1/3.35 | 16.75 | 0.1815 | 35.70 | 20.8 | 680 |
| 175 | 30/2.79 | 7/2.79 | 19.53 | 0.1576 | 79.80 | 23.6 | 1050 |
| 175 | 18/3.61 | 1/3.61 | 18.05 | 0.1563 | 41.10 | 22.1 | 780 |
| 200 | 30/3.00 | 7/3.00 | 21.00 | 0.1363 | 92.25 | 25.0 | 1190 |
| 200 | 18/3.86 | 1/3.86 | 19.30 | 0.1367 | 46.55 | 23.3 | 870 |
| Nominal Cross-Sectional Area | Stranding and Wire Diameter | Approx. Diameter of Bare Conductor | Calculated Resistance at 20 °C | Approx. Breaking Load | Approx. Overall Diameter | Approx. Mass |
|---|---|---|---|---|---|---|
| Type 16 | Type 16 | |||||
| mm² | No./mm | mm | Ω/km | kN | mm | kg/km |
| 25 | 7/2.34 | 7.02 | 1.094 | 8.44 | 10.6 | 170 |
| 50 | 7/3.30 | 9.90 | 0.5498 | 16.80 | 13.9 | 280 |
| 100 | 7/4.65 | 13.95 | 0.2769 | 33.30 | 18.0 | 470 |
| 150 | 19/3.48 | 17.40 | 0.1830 | 50.65 | 21.4 | 680 |
| 175 | 19/3.76 | 18.80 | 0.1568 | 59.10 | 22.8 | 780 |