ABC Cable (1+1 Core)
Low Voltage ABC Cable (1+1 Core)

ABC Cable (1+1 Core)

ZD CABLE’s Aerial Bounded Cable (ABC) is primarily used for overhead power lines. It is an excellent choice for supplying electricity to street lights, outdoor lighting systems, and temporary power for construction sites. ABC cable is designed to operate safely at a voltage of 0.6/1kV and can withstand outdoor weather conditions.

  • Designed with 2 wiresโ€”1 phase wire for power and 1 neutral wire.
  • Uses All Aluminum Alloy (AAAC) for the neutral wire to provide extra strength for hanging between poles.
  • Combines the conductivity of Aluminum (AAC) with the durability of Aluminum Alloy (AAAC).

ZD CABLE offers a durable Aerial Bounded Cable (ABC) designed for overhead power networks. ABC cable features a “1+1” core configuration, which is ideal for single-phase power distribution.

  • 1 Phase Conductor:ย Made of stranded, circular compacted aluminum (AAC).
  • 1 Neutral Conductor: Made of circular compacted aluminum alloy (AAAC). The aluminum alloy wire is stronger than the phase wire, allowing it to support the weight of the cable when installed overhead.

Both cores are covered with black Cross-linked polyethylene (XLPE) insulation. The insulation is tough and protects the wires from weather damage and sunlight (UV rays). ABC cable is rated for 0.6/1kV and works safely at conductor temperatures up to 90ยฐC.

Product Standards:

  • NF C 33-209 Insulated Cable Assembled with Harness for Overhead Network, with Rated Voltage of 0.6/1kV.
No. of Cores and Section (mmยฒ) No. of Wires (No.) Nominal Insulation Thickness (mm) Aprrox. Diameter of Cable (mm) Max. DC. Resistance at 20ยฐC (ฮฉ/km) Aprrox. Weight (kg/km)
2×16 7 1.2 14.4 1.91 131
2×25 7 1.4 17.6 1.20 200
2×35 7 1.6 20.4 0.868 273
2×50 7 1.6 22.6 0.641 350
2×70 12 1.8 26.8 0.443 495
2×95 19 1.8 30.4 0.320 656
2×120 19 1.8 32.8 0.253 799
4×16 7 1.2 17.4 1.91 262
4×25 7 1.4 21.3 1.20 399
4×35 7 1.6 24.7 0.868 547
4×50 7 1.6 27.3 0.641 699
4×70 12 1.8 32.4 0.443 990
4×95 19 1.8 36.8 0.320 1311
4×120 19 1.8 39.7 0.253 1597

No. of Cores and Section (mmยฒ) No. of Wires (Phase) (No.) No. of Wires (Neutral) (No.) Nominal Insulation Thickness (Phase) (mm) Nominal Insulation Thickness (Neutral) (mm) Approx. Diameter of Cable (mm) Max. DC. Resistance at 20ยฐC (Phase) (ฮฉ/km) Max. DC. Resistance at 20ยฐC (Neutral) (ฮฉ/km) Approx. Weight (kg/km)
1×25+1×54.6 7 7 1.4 1.6 21.3 1.20 0.63 309
1×35+1×54.6 7 7 1.6 1.6 22.7 0.868 0.63 345
1×50+1×54.6 7 7 1.6 1.6 23.8 0.641 0.63 384
1×70+1×54.6 12 7 1.8 1.6 25.9 0.443 0.63 456
1×95+1×54.6 19 7 1.8 1.6 27.7 0.320 0.63 537
1×70+1×70 12 7 1.8 1.6 26.7 0.443 0.50 491
1×95+1×70 19 7 1.8 1.6 28.5 0.320 0.50 571
1×120+1×70 19 7 1.8 1.6 29.7 0.253 0.50 643
1×120+1×95 19 19 1.8 1.6 31.9 0.253 0.343 737
1×150+1×95 19 19 1.8 1.6 33.6 0.206 0.343 819
3×25+1×54.6 7 7 1.4 1.6 23.5 1.20 0.63 508
3×35+1×54.6 7 7 1.6 1.6 26.1 0.868 0.63 619
3×50+1×54.6 7 7 1.6 1.6 28.1 0.641 0.63 733
3×70+1×54.6 12 7 1.8 1.6 31.9 0.443 0.63 951
3×95+1×54.6 19 7 1.8 1.6 35.2 0.320 0.63 1192
3×70+1×70 12 7 1.8 1.6 32.4 0.443 0.50 986
3×95+1×70 19 7 1.8 1.6 35.6 0.320 0.50 1227
3×120+1×70 19 7 1.8 1.6 37.8 0.253 0.50 1441
3×120+1×95 19 19 1.8 1.6 39.1 0.253 0.343 1536
3×150+1×95 19 19 1.8 1.6 42.2 0.206 0.343 1779

No. of Cores and Section (mmยฒ) No. of Wires (Phase) (No.) No. of Wires (Neutral) (No.) No. of Wires (Public Lighting) (No.) Nominal Insulation Thickness (Phase) (mm) Nominal Insulation Thickness (Neutral) (mm) Nominal Insulation Thickness (Public Lighting) (mm) Approx. Diameter of Cable (mm) Max. DC. Resistance at 20ยฐC (Phase) (ฮฉ/km) Max. DC. Resistance at 20ยฐC (Neutral) (ฮฉ/km) Max. DC. Resistance at 20ยฐC (Public Lighting) (ฮฉ/km) Approx. Weight (kg/km)
3×25+1×54.6+1×16 7 7 7 1.4 1.6 1.2 30.1 1.20 0.63 1.91 571
3×35+1×54.6+1×16 7 7 7 1.6 1.6 1.2 32.9 0.868 0.63 1.91 682
3×50+1×54.6+1×16 7 7 7 1.6 1.6 1.2 35.1 0.641 0.63 1.91 797
3×70+1×54.6+1×16 12 7 7 1.8 1.6 1.2 39.3 0.443 0.63 1.91 1014
3×70+1×54.6+1×25 12 7 7 1.8 1.6 1.4 39.3 0.443 0.63 1.20 1049
3×70+1×70+1×16 12 7 7 1.8 1.6 1.2 40.1 0.443 0.50 1.91 1049
3×95+1×70+1×16 19 7 7 1.8 1.6 1.2 43.7 0.320 0.50 1.91 1290
3×120+1×70+1×16 19 7 7 1.8 1.6 1.2 46.1 0.253 0.50 1.91 1504
3×120+1×95+1×16 19 19 7 1.8 1.6 1.2 48.3 0.253 0.343 1.91 1598
3×150+1×95+1×16 19 19 7 1.8 1.6 1.2 51.7 0.206 0.343 1.91 1842
3×25+1×54.6+2×16 7 7 7 1.4 1.6 1.2 30.1 1.20 0.63 1.91 637
3×35+1×54.6+2×16 7 7 7 1.6 1.6 1.2 32.9 0.868 0.63 1.91 748
3×50+1×54.6+2×16 7 7 7 1.6 1.6 1.2 35.1 0.641 0.63 1.91 862
3×70+1×54.6+2×16 12 7 7 1.8 1.6 1.2 39.3 0.443 0.63 1.91 1080
3×70+1×54.6+2×25 12 7 7 1.8 1.6 1.4 39.3 0.443 0.63 1.20 1148
3×70+1×70+2×16 12 7 7 1.8 1.6 1.2 40.1 0.443 0.50 1.91 1114
3×95+1×70+2×16 19 7 7 1.8 1.6 1.2 43.7 0.320 0.50 1.91 1356
3×120+1×70+2×16 19 7 7 1.8 1.6 1.2 46.1 0.253 0.50 1.91 1570
3×120+1×95+2×16 19 19 7 1.8 1.6 1.2 48.3 0.253 0.343 1.91 1664
3×150+1×95+2×16 19 19 7 1.8 1.6 1.2 51.7 0.206 0.343 1.91 1907