BARE CONDUCTOR
Copper Stranded Conductor to BS 7884 is a bare overhead conductor built from concentric layers of hard-drawn wires, supplied either in high-conductivity copper or in copper-cadmium alloy C108. It is meant for overhead power lines and for the overhead lines of electric traction systems. The TDS lists 20 copper constructions from 7/1.35 to 37/2.50 (10 to 185 mm²) and 21 copper alloy constructions from 3/2.30 to 19/4.00 (12 to 240 mm²).
BS 7884 deals with round conductors, solid or stranded, made of hard-drawn high-conductivity copper or of copper alloy for overhead power transmission and overhead electric traction. It sets the material, the dimensions, the mechanical and electrical properties and the stranding of these conductors (BS 7884 Clause 1). This page covers the stranded types: a straight centre wire surrounded by one or more helical layers of wires of equal diameter, each layer running in the opposite direction to the layer below (BS 7884 Clause 3.2).
| Wires in Conductor | Layer of 3 Wires | Layer of 6 Wires | Layer of 12 Wires | Layer of 18 Wires |
|---|---|---|---|---|
| 3 | 11 to 16 | – | – | – |
| 7 | – | 13 to 17 | – | – |
| 19 | – | 13 to 17 | 12 to 15 | – |
| 37 | – | 13 to 17 | 12 to 15 | 10.5 to 13 |
The lay ratio is the length of one full turn of a wire divided by the outside diameter of the layer it belongs to (BS 7884 Clause 3.7 and Table 5).
| Property | Hard-Drawn Copper | Copper Alloy C108 |
|---|---|---|
| Resistivity at 20 °C | 0.01777 µΩ·m | 0.02155 µΩ·m |
| Conductivity | 97% IACS | 80% IACS |
| Density used for the masses | 8890 kg/m³ | 8945 kg/m³ |
These figures come from BS 7884 Clause 4.4 and the notes to Tables 3 and 4. In the TDS, the nominal resistance follows from the nominal wire diameter and the average lay ratio, while the maximum resistance follows from the smallest permitted wire diameter and the shortest lay ratio. The minimum breaking load of each conductor is the total of the minimum breaking loads of its wires times 0.92 for 3-wire and 7-wire conductors, or times 0.90 for 19-wire and 37-wire conductors. Overall diameters are approximate.
Copper Stranded Conductor to BS 7884 is stranded from hard-drawn copper or copper-cadmium alloy wires for overhead lines. The table below sums up the requirements of the standard; the properties of each construction are listed in the TDS tab.
| Applicable Standard | BS 7884 |
|---|---|
| Standard Scope | Solid and stranded round conductors of hard-drawn copper and copper alloy for overhead power transmission and overhead electric traction |
| Conductor Materials | Hard-drawn high-conductivity copper (BS 6926 grade C100, C101 or C102) or hard-drawn copper-cadmium alloy C108 (BS 2873) |
| Copper Constructions | 3, 7, 19 and 37 wires; 20 sizes, 10 to 185 mm² |
| Copper Alloy Constructions | 3, 7, 19 and 37 wires; 21 sizes, 12 to 240 mm² |
| Overall Diameter | Approx. 4.05 to 17.75 mm (copper); 4.95 to 20.00 mm (copper alloy) |
| Resistivity at 20 °C | 0.01777 µΩ·m, 97% IACS (copper); 0.02155 µΩ·m, 80% IACS (copper alloy) |
| Minimum Breaking Load | 3752 N to 68860 N (copper); 6968 N to 117900 N (copper alloy) |
| Mass Tolerance | Wire and conductor mass per length no more than 2% over nominal |
| Wire Roundness | Within 2% of the nominal wire diameter |
| Lay Ratio | 11 to 16 for 3-wire conductors; 13 to 17, 12 to 15 and 10.5 to 13 for the 6-, 12- and 18-wire layers |
| Lay Direction | Opposite in adjacent layers; outer layer right-hand unless left-hand is ordered |
| Joints | Cold pressure welds; brazed or resistance-welded joins also allowed above seven wires; at least 15 m apart |
| Wrap Test | No breakage for copper wires under 5.6 mm and copper alloy wires under 3.5 mm |
| Identification | One tinned wire in the outer layer, on request |
Please state the quantity; the standard, BS 7884; the conductor material, copper or copper alloy; the construction as number of wires and wire diameter, for example 19/2.50; whether the outer layer is to be left-hand; whether you wish to witness tests on the stranded conductor; delivery needs such as coil size or spool type; whether a declaration of conformity or a report of inspection results is needed, and which tests; any special surface condition such as greased wires; any special marking, labelling or packing; and any required mass or length per coil or spool.
| Nominal Area of Cross-Section | Stranding and Wire Diameter | Approx. Overall Diameter | Nominal Mass | Resistance at 20 °C | Minimum Breaking Load | |
|---|---|---|---|---|---|---|
| Nominal | Max. | |||||
| mm² | No./mm | mm | kg/km | Ω/km | Ω/km | N |
| 10 | 7/1.35 | 4.05 | 89.82 | 1.788 | 1.829 | 3752 |
| 14 | 7/1.60 | 4.80 | 126.2 | 1.273 | 1.303 | 5267 |
| 16 | 3/2.65 | 5.70 | 148.3 | 1.082 | 1.106 | 6194 |
| 16 | 7/1.70 | 5.10 | 142.4 | 1.128 | 1.154 | 5946 |
| 25 | 7/2.10 | 6.30 | 217.3 | 0.7391 | 0.7563 | 9073 |
| 32 | 3/3.75 | 8.06 | 296.9 | 0.5405 | 0.5520 | 12400 |
| 32 | 7/2.46 | 7.38 | 298.2 | 0.5386 | 0.5497 | 12442 |
| 35 | 7/2.50 | 7.50 | 308.0 | 0.5215 | 0.5337 | 12860 |
| 50 | 7/3.00 | 9.00 | 443.5 | 0.3622 | 0.3706 | 18520 |
| 50 | 19/1.80 | 9.00 | 435.8 | 0.3727 | 0.3819 | 17700 |
| 70 | 7/3.55 | 10.65 | 621.1 | 0.2586 | 0.2646 | 25930 |
| 70 | 19/2.10 | 10.50 | 593.2 | 0.2738 | 0.2806 | 24090 |
| 95 | 19/2.50 | 12.50 | 840.7 | 0.1932 | 0.1980 | 34140 |
| 100 | 7/4.30 | 12.90 | 911.2 | 0.1763 | 0.1810 | 36540 |
| 120 | 19/2.80 | 14.00 | 1055 | 0.1540 | 0.1578 | 42830 |
| 125 | 19/2.90 | 14.50 | 1131 | 0.1436 | 0.1471 | 45940 |
| 150 | 19/3.20 | 16.00 | 1377 | 0.1180 | 0.1208 | 55940 |
| 150 | 37/2.25 | 15.75 | 1334 | 0.1233 | 0.1264 | 53880 |
| 185 | 19/3.55 | 17.75 | 1695 | 0.09582 | 0.09815 | 68860 |
| 185 | 37/2.50 | 17.50 | 1647 | 0.09981 | 0.1024 | 66490 |
| Nominal Area of Cross-Section | Stranding and Wire Diameter | Approx. Overall Diameter | Nominal Mass | Resistance at 20 °C | Minimum Breaking Load | |
|---|---|---|---|---|---|---|
| Nominal | Max. | |||||
| mm² | No./mm | mm | kg/km | Ω/km | Ω/km | N |
| 12 | 3/2.30 | 4.95 | 112.4 | 1.743 | 1.780 | 6968 |
| 16 | 7/1.70 | 5.10 | 143.3 | 1.368 | 1.399 | 8883 |
| 22 | 7/2.00 | 6.00 | 198.3 | 0.9882 | 1.011 | 12290 |
| 25 | 7/2.10 | 6.30 | 218.7 | 0.8959 | 0.9171 | 13550 |
| 30 | 7/2.30 | 6.90 | 262.3 | 0.7469 | 0.7645 | 16260 |
| 35 | 7/2.50 | 7.50 | 309.9 | 0.6324 | 0.6471 | 19210 |
| 38 | 7/2.60 | 7.80 | 335.2 | 0.5847 | 0.5983 | 20780 |
| 45 | 7/2.90 | 8.70 | 417.0 | 0.4698 | 0.4809 | 24600 |
| 55 | 7/3.20 | 9.60 | 507.8 | 0.3859 | 0.3950 | 29950 |
| 70 | 19/2.10 | 10.50 | 596.8 | 0.3316 | 0.3403 | 35990 |
| 75 | 7/3.70 | 11.10 | 678.8 | 0.2887 | 0.2954 | 38010 |
| 95 | 19/2.50 | 12.50 | 845.9 | 0.2343 | 0.2400 | 51010 |
| 100 | 7/4.30 | 12.90 | 916.9 | 0.2138 | 0.2195 | 51160 |
| 120 | 19/2.80 | 14.00 | 1061 | 0.1862 | 0.1914 | 60890 |
| 125 | 19/2.90 | 14.50 | 1138 | 0.1739 | 0.1784 | 65310 |
| 150 | 19/3.20 | 16.00 | 1386 | 0.1428 | 0.1465 | 79530 |
| 150 | 37/2.25 | 15.75 | 1342 | 0.1493 | 0.1533 | 80490 |
| 180 | 19/3.50 | 17.50 | 1658 | 0.1196 | 0.1225 | 95140 |
| 180 | 37/2.50 | 17.50 | 1657 | 0.1209 | 0.1242 | 99330 |
| 200 | 19/3.70 | 18.50 | 1853 | 0.1068 | 0.1696 | 100900 |
| 240 | 19/4.00 | 20.00 | 2165 | 0.09153 | 0.09378 | 117900 |
Product Inquiry
Please send your required cable designation, number of conductors, nominal cross-section, support cable type, rated voltage, packing length, and project standard.