AAC Conductor ZD CABLE

BARE CONDUCTOR

AAC Conductor ASTM B231

AAC Conductor (All Aluminum Conductor) is a homogeneous hard-drawn aluminium 1350 concentric-lay stranded overhead conductor manufactured in accordance with ASTM B231/B231M for bare and weather-resistant covered overhead electrical applications. Each conductor is identified by an industry code word from Aluminum Association Publication 50 (Rose, Iris, Marigold, Bluebonnet, etc.) combined with conductor size in AWG or kcmil; under ASTM B231 classification, Class AA is intended for bare overhead lines and Class A for covered weather-resistant applications or bare service where greater flexibility is required. The conductor is designed for overhead transmission and distribution where high conductivity, light weight and low installed cost take priority over tensile reserve, and is the standard bare aluminium conductor specification in North America and other markets following ASTM standards.

AAC Conductor under ASTM B231/B231M is a bare or weather-resistant overhead stranded conductor composed exclusively of hard-drawn aluminium 1350 wires. With the highest conductivity-to-area ratio of any overhead aluminium conductor in the ASTM family, AAC is the standard choice for overhead distribution lines, substation bus work and service drops where corrosion resistance and electrical conductivity outweigh the tensile reserve advantage of a steel-cored ACSR.

Conductor Construction

  • Material: Round hard-drawn aluminium 1350 wires conforming to ASTM B230/B230M (temper H19, extra hard, for Class AA and Class A) or ASTM B609/B609M (intermediate and annealed tempers H16, H26, H14, H24, H142, H242 for other classes).
  • Stranding: Concentric lay around a single central wire, with adjacent layers stranded in reverse directions; the outside layer is right-hand lay for Class AA and Class A, left-hand for Classes B, C and D unless otherwise specified by the purchaser.
  • Layer build-up: Centre wire + 6 + 12 + 18 + 24 + 30 wires per successive layer, yielding standard wire counts of 7, 19, 37, 61, 91 and 127 across the size range.
  • Lay ratio (Class AA, 7 wires and above): Preferred 13.5 × the outside diameter of the layer, with a permitted range of 10 to 16 times the diameter.
  • Lay ratio (Classes A, B, C, D): 8 to 16 × the outside diameter of the layer, except that for conductors of 37 wires or more this requirement applies only to the two outer layers.
  • Surface finish: Free of all imperfections inconsistent with good commercial practice.
  • Joints: For bare overhead Class AA and Class A 7-wire conductors, only cold-pressure welds or electric-butt cold-upset welds are permitted in the six outer wires, with no welds in the central wire. Minimum joint spacing follows the ASTM B231 schedule — 50 ft [15 m] apart for Class AA / A 7- and 19-wire constructions, 25 ft [7.5 m] for 37-wire, 5 ft [1.5 m] for 61-wire and larger.

AAC Code Word Designations

Code Word Conductor Size Description
Rose 4 AWG (21.1 mm²) Small-size 7-wire Class A conductor for service drops and weather-resistant covered applications
Aster 2/0 AWG (67.4 mm²) 7-wire conductor available in both Class AA and Class A for distribution-line work
Tulip 336.4 kcmil (170.5 mm²) 19-wire Class A conductor widely used as a primary distribution feeder
Marigold 1113 kcmil (564.0 mm²) 61-wire Class AA / Class A bare conductor for distribution substation bus and short transmission spans
Coreopsis 1590 kcmil (805.7 mm²) 61-wire Class AA bare conductor; one of the largest AAC sizes commonly used for substation bus work
Bluebonnet 3500 kcmil (1773 mm²) 127-wire Class A conductor — the largest size listed in ASTM B231 Table 1

Code words for AAC sizes are assigned under Aluminum Association Publication 50 and follow a flower-name convention that is part of the practical procurement vocabulary in North America even though the names themselves are not part of the ASTM formal definition. Within ASTM B231, conductors are classified by Class AA (bare overhead), Class A (covered weather-resistant or bare with greater flexibility), Class B (insulated), and Classes C and D (greater flexibility for insulated cable cores). For sizes available in both Class AA and Class A, the Class AA version typically uses the lower wire count (e.g. Sneezewort 250 kcmil 7-wire or Cosmos 477 kcmil 19-wire) for stiffer bare overhead service, while the Class A version uses a higher wire count (e.g. Valerian 250 kcmil 19-wire or Syringa 477 kcmil 37-wire) for greater flexibility.

Rated tensile strength of AAC under ASTM B231 is calculated as a rating factor multiplied by the sum of the minimum tensile strengths of the component wires. The rating factors decrease with stranding layer count: 96% for 7-wire (single-layer), 93% for 19-wire (two-layer), 91% for 37-wire (three-layer), 90% for 61-wire (four-layer), and 89% for 91-wire and 127-wire (five-layer and above) constructions. Mass and electrical resistance per unit length include stranding increments of 2% for sizes below 1000 mm², 3% for 1000–1500 mm², and 4% for 1500–2000 mm²; the maximum d.c. resistance of any stranded conductor shall not exceed 2% over the nominal value at 20°C.

Typical Applications

  • Overhead bare distribution lines in urban and rural networks (most common application of Class AA)
  • Substation bus work and short jumpers between switchgear and transformers (medium-to-large sizes 397.5–1590 kcmil)
  • Service drops and tap connections from distribution feeders (small sizes 4 AWG to 4/0 AWG)
  • Weather-resistant covered overhead conductors (Class A, in factory-applied PE or XLPE covering)
  • Insulated cable conductor cores requiring greater flexibility (Class B, C and D for building wire and power cables)
  • Coastal and chemical-industrial overhead networks where the corrosion resistance of all-aluminium construction favours AAC over ACSR

AAC manufactured to ASTM B231/B231M is functionally equivalent to IEC 61089 type code A1 (with wire material per IEC 889), GB/T 1179 JL designation, BS EN 50182 AL1 series and AS 1531 — allowing the same conductor to be supplied against multiple international procurement standards. The ASTM code-word convention (Rose, Pansy, Marigold, etc.) is the practical procurement identifier in North America and is referenced in utility specifications even when an international standard is invoked.

AAC Conductor is manufactured in accordance with ASTM B231/B231M as a hard-drawn aluminium 1350 concentric-lay stranded conductor for bare and weather-resistant overhead use, with wire material per ASTM B230/B230M (H19 temper) or ASTM B609/B609M (other tempers). The conductor is identified by Aluminum Association Publication 50 code words combined with size in AWG or kcmil.

Technical Characteristics

Applicable Standard ASTM B231/B231M
Standard Scope Concentric-lay-stranded aluminum 1350 conductors made from round hard-drawn aluminium wires for general electrical purposes — bare overhead, covered weather-resistant, and insulated applications
Cross-Reference Standards IEC 61089 (type code A1, wire material per IEC 889); GB/T 1179 (JL); BS EN 50182 (AL1 series); AS 1531
Aluminium Material Hard-drawn aluminium 1350 (formerly EC aluminium, UNS A91350) per ASTM B230/B230M for H19 temper or ASTM B609/B609M for H16, H26, H14, H24, H142, H242 tempers
Class Designations Class AA (bare overhead), Class A (covered weather-resistant or flexible bare), Class B (insulated cable conductors), Class C and Class D (greater flexibility for insulated cable cores)
Code Word Convention Aluminum Association Publication 50 — flower names assigned to each conductor size (Rose, Pansy, Marigold, Bluebonnet, and others)
Stranding Concentric-lay, adjacent layers in reverse directions; outside layer right-hand for Class AA and Class A, left-hand for Class B, C and D
Standard Wire Counts 7, 19, 37, 61, 91, 127 wires
Lay Ratio — Class AA Outside Layer Preferred 13.5 × outside diameter; permitted range 10 to 16
Lay Ratio — Other Classes 8 to 16 × outside diameter of the layer (applies to the two outer layers for 37-wire and larger)
Direction of Lay — Outer Layer Right-hand for Class AA and Class A; left-hand for Class B, C and D, unless otherwise specified by the purchaser
Nominal Cross-Section Range 13.3 mm² (6 AWG, Peachbell) to 1773 mm² (3500 kcmil, Bluebonnet)
Cross-Section Tolerance Cross-sectional area of the completed conductor not less than 98% of the nominal listed in ASTM B231 Tables 1–4
Mass and Resistance Increment due to Stranding 2% (sizes < 1000 mm²); 3% (1000–1500 mm²); 4% (1500–2000 mm²)
D.C. Resistance Tolerance Maximum d.c. resistance not exceeding 2% over the nominal value at 20 °C
Density 2705 kg/m³ at 20 °C (aluminium 1350)
Rated Strength Rating Factor 96% (7-wire / 1 layer); 93% (19-wire / 2 layers); 91% (37-wire / 3 layers); 90% (61-wire / 4 layers); 89% (91-wire and 127-wire / 5+ layers) — per ASTM B231 Table 6
Maximum Continuous Operating Temperature 75 °C (typical bare overhead limit for hard-drawn 1350-H19; site-specific ampacity to be verified against ambient and loading conditions)
Surface Finish Free of all imperfections inconsistent with good commercial practice
Code Name Conductor Size Number of Wires Diameter of Wire Approx. Overall Diameter Unit Weight Nominal Breaking Load Nominal DC Resistance at 20°C
Nominal Actual
AWG or kcmil mm² No. mm mm kg/km kN ohm/km
7-Wire Construction (Single Aluminium Layer)
Peachbell 6 13.3 7 1.56 4.68 36.6 2.53 2.1606
Rose 4 21.1 7 1.96 5.88 58.2 3.91 1.3619
Iris 2 33.6 7 2.47 7.41 92.6 5.99 0.8550
Pansy 1 42.4 7 2.78 8.34 116.6 7.30 0.6779
Poppy 1/0 53.5 7 3.12 9.36 147.2 8.84 0.5373
Aster 2/0 67.4 7 3.50 10.50 185.7 11.1 0.4262
Phlox 3/0 85.0 7 3.93 11.79 233.9 13.5 0.3379
Oxlip 4/0 107.2 7 4.42 13.26 295.2 17.0 0.2680
Sneezewort 250 126.7 7 4.80 14.40 348.8 20.1 0.2268
Daisy 266.8 135.2 7 4.96 14.88 372.3 21.4 0.2126
19-Wire Construction (Two Aluminium Layers)
Valerian 250 126.7 19 2.91 14.55 348.6 20.7 0.2268
Laurel 266.8 135.2 19 3.01 15.05 372.2 22.1 0.2126
Peony 300 152.0 19 3.19 15.95 418.3 24.3 0.1890
Tulip 336.4 170.5 19 3.38 16.90 469.5 27.3 0.1686
Daffodil 350 177.3 19 3.45 17.25 487.9 28.4 0.1621
Canna 397.5 201.4 19 3.67 18.35 554.9 31.6 0.1427
Goldentuft 450 228.0 19 3.91 19.55 627.6 35.0 0.1260
Cosmos 477 241.7 19 4.02 20.10 664.8 37.0 0.1189
Zinnia 500 253.3 19 4.12 20.60 697.1 38.9 0.1134
Dahlia 556.5 282.0 19 4.35 21.75 775.8 43.3 0.1019
37-Wire Construction (Three Aluminium Layers)
Syringa 477 241.7 37 2.88 20.16 664.8 38.6 0.1189
Hyacinth 500 253.3 37 2.95 20.65 696.8 40.5 0.1134
Mistletoe 556.5 282.0 37 3.12 21.84 775.7 44.3 0.1019
Meadowsweet 600 304.0 37 3.23 22.61 836.3 47.5 0.0945
Orchid 636 322.3 37 3.33 23.31 886.9 50.4 0.0892
Heuchera 650 329.4 37 3.37 23.59 907.4 51.7 0.0872
Verbena 700 354.7 37 3.49 24.43 975.7 55.4 0.0810
Violet 715.5 362.6 37 3.53 24.71 998.5 56.7 0.0793
Petunia 750 380.0 37 3.62 25.34 1046 58.6 0.0756
Arbutus 795 402.8 37 3.72 26.04 1109 61.8 0.0713
Cockscomb 900 456.0 37 3.96 27.72 1256 68.4 0.0630
Magnolia 954 483.4 37 4.08 28.56 1331 72.6 0.0594
Hawkweed 1000 506.7 37 4.18 29.26 1395 76.2 0.0567
Bluebell 1033.5 523.7 37 4.25 29.75 1441 78.8 0.0549
61-Wire Construction (Four Aluminium Layers)
Flag 700 354.7 61 2.72 24.48 975.8 57.1 0.0810
Nasturtium 715.5 362.6 61 2.75 24.75 998.5 58.4 0.0793
Cattail 750 380.0 61 2.82 25.38 1046 60.3 0.0756
Lilac 795 402.8 61 2.90 26.10 1110 63.8 0.0713
Snapdragon 900 456.0 61 3.09 27.81 1256 70.8 0.0630
Goldenrod 954 483.4 61 3.18 28.62 1331 75.0 0.0594
Camellia 1000 506.7 61 3.25 29.25 1394 78.3 0.0567
Larkspur 1033.5 523.7 61 3.31 29.79 1442 81.3 0.0549
Marigold 1113 564.0 61 3.43 30.87 1553 87.3 0.0509
Hawthorn 1192.5 604.2 61 3.55 31.95 1662 93.5 0.0476
Narcissus 1272 644.5 61 3.67 33.03 1774 98.1 0.0446
Columbine 1351 684.6 61 3.78 34.02 1884 104 0.0420
Carnation 1431 725.1 61 3.89 35.01 1997 108 0.0396
Gladiolus 1510.5 765.4 61 4.00 36.00 2108 114 0.0375
Coreopsis 1590 805.7 61 4.10 36.90 2216 120 0.0357
Jessamine 1750 886.7 61 4.30 38.70 2442 132 0.0324
91-Wire Construction (Five Aluminium Layers)
Cowslip 2000 1013 91 3.77 41.47 2787 153 0.0284
Sagebrush 2250 1140 91 3.99 43.89 3166 167 0.0255
Lupine 2500 1267 91 4.21 46.31 3519 186 0.0229
Bitterroot 2750 1393 91 4.42 48.62 3872 205 0.0208
127-Wire Construction (Six Aluminium Layers)
Trillium 3000 1520 127 3.90 50.70 4226 223 0.0191
Bluebonnet 3500 1773 127 4.22 54.86 4977 261 0.0165
Download Datasheet PDF

Electrical Tests

  • Verification of individual aluminium wire properties before stranding against ASTM B230/B230M (1350-H19) or ASTM B609/B609M (other tempers), including resistivity at 20 °C determined per ASTM B193 and minimum tensile strength
  • Verification of conductor cross-sectional area by either (a) calculation from diameter measurements of component wires expressed to four decimal places, perpendicular to wire axes; or (b) ASTM B263 weight-and-length method, with the actual stranding mass increment used in case of dispute
  • Direct-current resistance measurement at 20 °C (or corrected to 20 °C using ASTM B231 Table 8 temperature multiplying factors), with the maximum d.c. resistance not exceeding 2% over the nominal tabulated value

Mechanical Tests

  • Breaking-strength test on the completed conductor, requiring breaking strength not less than the rated strength of 1350-H19 conductors if failure occurs in the free length at least 1 in. [25 mm] beyond either gripping device, or not less than 95% of the rated strength if failure occurs within 1 in. of the grips; free length between grips not less than 24 in. [600 mm]
  • Tensile strength test on individual wires removed from the completed conductor (when requested by the purchaser), requiring not less than 95% of the minimum tensile strength specified in ASTM B230/B230M for 1350-H19, or 95–105% of the specified range for B609/B609M intermediate and annealed tempers
  • Bending properties verification on wires composing the conductor, demonstrating compliance with ASTM B230/B230M bending requirements after stranding
  • Aluminium-wire joint strength verification: cold-pressure welds, electric-butt cold-upset welds and (for non-AA/A bare-overhead conductors) electric-butt welds, with minimum spacing per ASTM B231 Table 5 — 50 ft [15 m] for Class AA / A 7- and 19-wire, 25 ft [7.5 m] for 37-wire, 5 ft [1.5 m] for 61-wire and larger, and 1 ft [0.3 m] for Class B / C / D

Physical and Material Tests

  • Wire diameter measurement using a micrometer caliper, with diameter values expressed to four decimal places when used in cross-sectional area calculation
  • Overall conductor diameter calculated as the numerical sum of strand-wire component diameters (the “mean diameter” method), with minimum and maximum overall diameters derived from ASTM B230/B230M mean-diameter tolerances of the strand wire
  • Lay length and direction-of-lay verification on every stranded layer against the limits of ASTM B231 Section 7 — preferred 13.5 × diameter for Class AA outside layer, 10–16 range for other Class AA layers and Class A, 8–16 for Classes B, C and D
  • Surface inspection on the completed conductor for absence of imperfections inconsistent with good commercial practice
  • Aluminium-wire joint count and spacing verification per ASTM B231 Table 5 and Section 6